Cardax Prox Mifare Series Installation Note page 6

Teardrop
Hide thumbs Also See for Prox Mifare Series:
Table of Contents

Advertisement

Connections
The Prox Mifare Series (Teardrop) reader connects to one of the following:
• Cardax FT Controller 3000
• Cardax FT Reader I/O Interface
• Cardax FT URI
• Cardax Commander URI
Use the cable terminating tool to connect the cables to the socket as described
in the following sections.
Pin number 4 of the Prox Mifare Series (Teardrop) reader connector feeds into
the cable terminating tool first.
Connecting to the Cardax FT Controller 3000
The Cardax FT Controller 3000 interfaces the following types of reader into
the Cardax FT Command Centre system:
• Cardax IV readers, including Prox Mifare Series (Teardrop) readers
• Wiegand readers
Each Cardax FT Controller 3000 can interface up to eight Prox Mifare Series
(Teardrop) readers into the Cardax FT Command Centre system.
The ports to which the Prox Mifare Series (Teardrop) reader can connect are
set up as four distinct groups (numbered 1 to 4). Each group provides
connection for two Prox Mifare Series (Teardrop) readers or other Cardax IV
readers. Refer to the following diagram for the location of the ports on the
Cardax FT Controller 3000.
P4
P4
RS485
P2
PF4
PF3
PF2
PF1
6
P3
DETECTOR
LED
PE4
PD4
PC4
PD 4
PC4
PE3
PD3
PC3
PD3
PC3
PE2
PD2
PC2
PD2
PC2
PE1
PD1
PC1
PD1
PC1
PB1 to PB4
PC1 to PC4
2 x Cardax IV Readers
Inputs
per connector
pin 1 = Input 1
pin 2 = Ground
Reader 1 = pins 1 & 3
pin 3 = Input 2
Reader 2 = pins 2 & 4
Pin 1 = Reader 1 transmit
Pin 2 = Reader 2 transmit
Pin 3 = Reader 1 receive
Pin 4 = Reader 2 receive
P1
J1 to J4
RS485
terminating resistors
PB4
PA4
Group 4
PA4
POWER
OUT
Group 3
PB3
PA3
PA3
POWER
OUT
Group 2
PB2
PA2
PA2
POWER
OUT
Group 1
PB1
PA1
PA1 to PA4
PA1
POWER
OUT
Power Out
pin 1 = power out
pin 2 = 0 V
Part number 3E1100 R12
June 2007