) type VCP-W (K = 1) vacuum circuit breaker through 15 kV rated symmetrical current basis (standard
a
ratings).
Identification
Circuit
Nominal
breaker
voltage
type
class
kV
50VCP-W 25
4.16
50VCP-W 40
4.16
50VCP-W 50
4.16
50VCP-W 63
4.16
75VCP-W 40
7.2
75VCP-W 50
7.2
150VCP-W 25
13.8
150VCP-W 40
13.8
150VCP-W 50
13.8
150VCP-W 63
13.8
All circuit breakers are tested to 60 Hz; however, they can also be applied at 50 Hz with no derating.
a
Consult the Consulting Application Guide CA08104001E sections 1 and 5 for further information.
b
Also 3-second short time current carrying capability.
c
Table 6. (ANSI Standards
) type VCP-WXC circuit breaker through 15 kV rated symmetrical current basis (standard ratings).
a
See Figure 23 for control schemes and diagram that apply to this breaker. This breaker differs from the standard breaker with the addition of a third motor cut-off switch and
addition of two wires.
Identification
Rated voltage
Circuit
Voltage
Insulation level
breaker
withstand test
Max.
Voltage
type
voltage
range
factor
Power
freq-
uency
V
K
(1 min.)
kV rms
kV rms
150 VCP-WXC
17.5
1
42
63
All circuit breakers are tested to 60 Hz; however, they can also be applied at 50 Hz with no derating.
a
Optional interrupting time of 3 cycles is available.