General Specifications and ...
Adjustable Frequency Drive, P37K, T2
Cable
length (ft [m])
98.4 [30]
328 [100]
492.1 [150]
Table 8.24
Adjustable Frequency Drive, P45K, T2
Cable
length (ft [m])
98.4 [30]
328 [100]
492.1 [150]
Table 8.25
Adjustable Frequency Drive, P1K5, T4
8
8
Cable
length (ft [m])
16.4 [5]
164 [50]
492.1 [150]
Table 8.26
Adjustable Frequency Drive, P4K0, T4
Cable
length (ft [m])
16.4 [5]
164 [50]
492.1 [150]
Table 8.27
Adjustable Frequency Drive, P7K5, T4
Cable
length (ft [m])
16.4 [5]
164 [50]
492.1 [150]
Table 8.28
Adjustable Frequency Drive, P11K, T4
Cable
length (ft [m])
49.2 [15]
328 [100]
492.1 [150]
Table 8.29
8-24
®
VLT
HVAC Drive Design Guide
AC line
Rise time
voltage [V]
[μsec]
240
0.300
240
0.536
240
0.776
Rise time
AC line
voltage [V]
[μsec]
240
0.300
240
0.536
240
0.776
AC line
Rise time
voltage [V]
[μsec]
400
0.640
400
0.470
400
0.760
Rise time
AC line
voltage [V]
[μsec]
400
0.172
400
0.310
400
0.370
Rise time
AC line
voltage [V]
[μsec]
400
0.04755
400
0.207
400
0.6742
Rise time
AC line
voltage [V]
[μsec]
400
0.408
400
0.364
400
0.400
MG11BB22 - VLT
®
Vpeak
[kV]
0.598
0.566
0.546
Vpeak
[kV]
0.598
0.566
0.546
Vpeak
[kV]
0.690
0.985
1.045
Vpeak
[kV]
0.890
1.190
Vpeak
[kV]
0.739
1.040
1.030
Vpeak
[kV]
0.718
1.050
0.980
is a registered Danfoss trademark
dU/dt
[kV/μsec]
1.593
0.843
0.559
dU/dt
[kV/μsec]
1.593
0.843
0.559
dU/dt
[kV/μsec]
0.862
0.985
0.947
dU/dt
[kV/μsec]
4.156
2.564
1.770
dU/dt
[kV/μsec]
8.035
4.548
2.828
dU/dt
[kV/μsec]
1.402
2.376
2.000