Creating CFCs
6.6 Working with the CFC Editor
Procedure
1. Open the "General" tab and "Inputs/Outputs" tab in the "Object Properties" dialog box for
each block.
2. Enter the parameters for all blocks according to the table below.
90
Block
Block
name in
the project
Mul04
4
Pcs7AnIn
INPUT_U
Integral
INT_P
MonAnL
LIA
I/O
Meaning
In1.ST
Value 1 to multiply (BYTE)
In1.Value
Value 1 to multiply (REAL)
In4.Value
Invert sign for flow rate (proc‐
ess value) - Part of the fill level
simulation in raw materials tank
Feature.Bit29
Enables a substitute value
Mode
Measuring range 4 to 20 mA
Scale.High
High measuring range
SimOn.Value
Simulation value active
SimPV_In.Value
Raw materials tank level
SubsPV_In
Substitute value for SimPV_In
In.ST
Analog input value (BYTE)
In.Value
Simulation of the raw material
tank level
OutHiLim
High limit of the output value
OutTrk.ST
Predefined value used for Out‐
TrkOn = 1 (BYTE)
OutTrk.Value
Predefined value used for Out‐
TrkOn = 1 (REAL)
TI
Integration time
GradHDnEn
Gradient monitoring (high) for
negative changes
GradHUpEn
Gradient monitoring (high) for
positive changes
PV.ST
Process value (BYTE)
PV.Value
Process value (REAL)
PV_AH_En
PV alarm limit (high) deactiva‐
ted
PV_AH_Lim
High alarm limit = 490 m
PV_AL_Lim
Low alarm limit = 5 m
PV_Hyst
Hysteresis
PV_OpScale.High
High display limit of the proc‐
ess value in the container
PV_Unit
Unit of the PV in m3
PV_WH_En
PV warning limit (high) deacti‐
vated
PV_WH_Lim
High warning limit = 450 m
PCS 7 SMART Getting Started - Part 1 (V9.0 with APL)
Value
0
0
-1.0
1
16#0203
550
1
500
500
0
0.0
500
0
0
30
0
0
0
0
0
490
3
25
3
1
550
1034
0
450
3
Getting Started, 12/2017, A5E42181435-AA