(3) Wire the twisted pair shielded cable after stripping its sheath to make its cables loose.
Also, protect the shielded cable of the twisted pair shielded cable to ensure that it will not make contact
with the conductive area.
Cable stripping size
5mm
REMARKS
Information on bar terminals
Introduced products (as of August, 2005): Phoenix Contact Co.,Ltd.
Terminal Screw
Size
(with insulation sleeve)
M2
⋅ Bar terminal crimping tool: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
When using the bar terminal (without insulation sleeve),
use care so that the twisted wires do not come out.
(4) Loosen the terminal screw and insert the cable into the terminal.
Screw Size
Tightening Torque
M2
CAUTION
Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or
malfunction due to damage to the screw or unit.
Wire the stripped cable after twisting it to prevent it from becoming loose.
In addition, do not solder it.
Use a bar type terminal as required.
Bar Terminal Model
Al 0.5-6WH
0.22N⋅m to 0.25N⋅m
0.3mm
Bar Terminal Model
(without insulation sleeve)
A 0.5-6
Cable Size
2
2
to 0.75mm
(Tip thickness: 0.4mm/tip width: 2.5mm )
INSTALLATION
2
Wire Size (mm
)
0.3 to 0.5
Screwdriver
Small
flat-blade screwdriver
2
11

Advertisement