Hisense ADT-12UX4SSNL3 Technical & Service Manual page 99

Dc-inverter air conditioners, duct, cassette, ceiling & floor
Table of Contents

Advertisement

W
I
R
I
N
G
D
I
A
W
I
R
I
N
G
D
I
A
1
1
.
1
1
.
Static Pressure Setting
Setting of available of Static Pressure
The static pressure outside the indoor unit can be selected.
For AC MOTOR type:
You can change the static pressure by changing the fan motor terminal which refer to following figure.
Low static pressure
WHT
High static pressure
RED
Note:
*:Default Settings is low static pressure by factory.
The noise under high static pressure is higher than static pressure.
For DC MOTOR type :
The static pressure can be freely adjusted by using specific wire remote controller.
LCD
DC-� INVERTER AIR CONDITIONER TECHNICAL&SERVICE MANUAL
G
R
A
M
G
R
A
M
Error Indicator
Parameter Code
Function Code
Fan motor
Model
18K
Model
The range of
(Capacity
static pressure
Btu/h)
9K/12K
24K
36K
0-120Pa
42K/48K/60K
0-120Pa
High static
Low static
pressure
pressure
10Pa*
30Pa
Function code set
1-50,more than 50 is 50 Pa,
0-50Pa
[default: 0(0Pa)]
1-80,more than 80 is 80
0-80Pa
Pa,[default: 0(25Pa)]
1-120,more than 120 is 120 Pa,
[default: 47Pa)]
1-120,more than 120 is 120 Pa,
[default: 0(60Pa)]
97