1-1 Feat tures Duct t Type Ai r Conditio oner eatures Save Inst tallation Spac indoor unit c can be install led inside the e ceiling con nveniently. Optional S Static Pressu 8k: optional 1 10Pa /30Pa, 24K/36K 50 0Pa/80Pa 48 K/60K: 80Pa a/120Pa stati ic Pressure.
Page 5
Self Recovery of Power Break When the power supply is recovered after break, all preset are still effective and the air-conditioner can run according to the original setting. Fault Self-diagnose Function When there is something wrong with the air-conditioner,the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance.
Page 6
Cassette T Type Air C Condition eatures Save Inst tallation Spac The indoo or unit can b be installed in nside the ceil ling convenie ently. High Effic ciency and E nvironment F Friendly New w Refrigerant- -R410A R410A ca an protect th e environme ent and do no...
Page 7
Ceiling &Floor Air Conditioner Features Save Installation Space The indoor unit’s thickness is only 230mm,can be installed inside the ceiling conveniently. Flexible Installation Options According to the actual installation space,The indoor unit can be installed in the ceiling or on the floor. One unit, Two installation method. High Efficiency and Environment Friendly New Refrigerant-R410A R410A can protect the environment and do not harm to the ozone layer.
Page 8
Fault Self-diagnose Function When there is something wrong with the air-conditioner, the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance. ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
1-3 MODEL IDENTIFICATION A U C -18 U R 4 S Z A A 1 serial number K:Outdoor Unit Indetification G:Indoor Unit Indetification S:Refrigement R410A F:Refrigement R22 4:220V-240V/50HZ/1P 6:380V-415V/50HZ/3P X: Wire Romote Controller R:Wireless Romote Controller U:DC-Invert Heat Pump Type H:Heat Pump Type C:Cooling Only Cool Capacity:18x10 Btu/h Type:D-Duct Type,C-Cassette Type,V-Ceiling&Floor Type,W-Outdoor Unit Unit...
Page 11
-4 Produ ct Picture uct Typ AUD-18HX X4SUNL UD-24HX4SZLH AUD-36HX 6SAHH odel AUD-18HX 4SUNL1 UD-24HX4SZLH AUD-36HX6 6SAHH1 door tdoor UD-48HX6SPHH odel AUD-48HX 6SEHH1 UD-60HX6SPHH UD-60HX6SPHH door tdoor ON/OF FF UNITARY AIR R CONDITIONER R TECHNICAL& S SERVICE MANU UAL V5.0...
Page 12
assette T AUC-18HR R4SUAA UC-24HR4SZGA AUC-36HR 6SAGA odel AUC-18HR R4SUAA1 UC-24HR4SZGA AUC-36HR6 6SAGA1 door tdoor UC-48HR6SPHA odel AUC-48HR R6SEHA1 UC-60HR6SPHA UC-60HR6SPHA door tdoor ON/OF FF UNITARY AIR R CONDITIONER R TECHNICAL& S SERVICE MANU UAL V5.0...
Ceiling&Floor Type AUV-18HR4SUA AUV-24HR4SZA AUV-36HR6SAB Model AUV-18HR4SUA1 AUV-24HR4SZA1 AUV-36HR6SAB1 Indoor Outdoor AUV-48HR6SPC Model AUV-48HR6SEC1 AUV-60HR6SPC AUV-60HR6SPC1 Indoor Outdoor ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 14
DISPLAY PANEL Cassette Type 18k 24K,36K,48K,60K ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 15
Ceiling&Floor type ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 16
1-1 Feat tures Duct t Type Ai r Conditio oner eatures Save Inst tallation Spac indoor unit c can be install led inside the e ceiling con nveniently. Optional S Static Pressu 8k: optional 1 10Pa /30Pa, 24K/36K 50 0Pa/80Pa 48 K/60K: 80Pa a/120Pa stati ic Pressure.
Page 17
Self Recovery of Power Break When the power supply is recovered after break, all preset are still effective and the air-conditioner can run according to the original setting. Fault Self-diagnose Function When there is something wrong with the air-conditioner,the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance.
Page 18
Cassette T Type Air C Condition eatures Save Inst tallation Spac The indoo or unit can b be installed in nside the ceil ling convenie ently. High Effic ciency and E nvironment F Friendly New w Refrigerant- -R410A R410A ca an protect th e environme ent and do no...
Page 19
Ceiling &Floor Air Conditioner Features Save Installation Space The indoor unit’s thickness is only 230mm,can be installed inside the ceiling conveniently. Flexible Installation Options According to the actual installation space,The indoor unit can be installed in the ceiling or on the floor. One unit, Two installation method. High Efficiency and Environment Friendly New Refrigerant-R410A R410A can protect the environment and do not harm to the ozone layer.
Page 20
Fault Self-diagnose Function When there is something wrong with the air-conditioner, the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance. ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 21
1-2 Product Lineup Type Model Duct Type AUD- ● ● ● ● ● Cassette Type AUC- ● ● ● ● ● Ceiling&Floor AUV- ● ● ● ● ● type ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 22
1-3 MODEL IDENTIFICATION A U C -18 U R 4 S Z A A 1 Serial Number K:Outdoor Unit Indetification G:Indoor Unit Indetification S:Refrigerant R410A F:Refrigerant R22 4:220V-240V/50HZ/1P 6:380V-415V/50HZ/3P X: Wire Remote Controller R:Wireless Remote Controller U:DC-Invert Heat Pump Type H:Heat Pump Type C:Cooling Only Cool Capacity:18x10 Btu/h Type:D-Duct Type,C-Cassette Type,V-Ceiling&Floor Type,W-Outdoor Unit Unit...
Page 23
-4 Produ ct Picture uct Typ AUD-18HX X4SUNL UD-24HX4SZLH AUD-36HX 6SAHH odel AUD-18HX 4SUNL1 UD-24HX4SZLH AUD-36HX6 6SAHH1 door tdoor UD-48HX6SPHH odel AUD-48HX 6SEHH1 UD-60HX6SPHH UD-60HX6SPHH door tdoor ON/OF FF UNITARY AIR R CONDITIONER R TECHNICAL& S SERVICE MANU UAL V5.0...
Page 24
assette T AUC-18HR R4SUAA UC-24HR4SZGA AUC-36HR 6SAGA odel AUC-18HR R4SUAA1 UC-24HR4SZGA AUC-36HR6 6SAGA1 door tdoor UC-48HR6SPHA odel AUC-48HR R6SEHA1 UC-60HR6SPHA UC-60HR6SPHA door tdoor ON/OF FF UNITARY AIR R CONDITIONER R TECHNICAL& S SERVICE MANU UAL V5.0...
Page 25
Ceiling&Floor Type AUV-18HR4SUA AUV-24HR4SZA AUV-36HR6SAB Model AUV-18HR4SUA1 AUV-24HR4SZA1 AUV-36HR6SAB1 Indoor Outdoor AUV-48HR6SPC Model AUV-48HR6SEC1 AUV-60HR6SPC AUV-60HR6SPC1 Indoor Outdoor ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 26
DISPLAY PANEL Cassette Type 18k 24K,36K,48K,60K ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 27
Ceiling&Floor type ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
& & 4.2MAX. Refrigerant pipe length and height difference: *Do your best to reduce the pipe length. Long pipe may cause capacity of the indoor unit incline. Total refrigerant pipe length Outdoor unit precharged 0m~5m Exceed 5m AUW-18H4SU Xg = 15g / m × (Total pipe length(m) ‐5) 1200g 0g AUW-24H4SZ 1650g 0g AUW-36H6SA 2300g 0g Xg =35g / m × (Total pipe length(m) ‐5) AUW-48H6SP 3100g 0g AUW-60H6SP 3300g 0g ...
& & 4.3ELECTRIC Diagrams 18K 24K 36K/48K/60K UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 57
& & Recommend Wire Size Power Source Transmitting Cable Model POWER SUPPLY Cable Size Size Capacity(Btu/h) (mm2) (mm2) 220-240V ~,50Hz 3×1.5 5×1.5 220-240V ~,50Hz 3×2.5 4×0.75 380-415V ~,3N~,50Hz 5×1.5 4×0.75 380-415V ~,3N~,50Hz 48K/60K 5×2.5 4×0.75 ● Use an ELB (Electric Leakage Breaker). If not used, it will cause an electric shock or a fire.
Page 58
& & cord (code designation H05RN-F) . 3) Use a shielded cable for the transmitting circuit and connect it to ground . 4) In the case that power cables are connected in series, add each unit maximum current and select wires below. * in the case that current exceeds 63A, do not connect cables in series.
& & 4-4Air flow and ESP Chart Diagrams(for duct type) 18K 18K Curve for 10Pa ESP 1000 Air flow(m3/h) 18K Curve for 30Pa ESP 1000 1100 Air flow(m3/h) UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 60
& & 24K 24K Curve for 50Pa ESP 700 800 900 1000 1100 1200 1300 1400 Air flow(m3/h) 24K Curve for 80Pa ESP 600 700 800 900 1000 1100 1200 1300 1400 1500 Air flow(m3/h) UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 61
& & 36K Curve for 50Pa ESP 900 1100 1300 1500 1700 1900 Air flow(m3/h) 36K Curve for 80Pa ESP 800 1000 1200 1400 1600 1800 2000 Air flow(m3/h) UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 62
& & 48K 48K Curve for 80Pa ESP 1500 1700 1900 2100 2300 2500 Air Flow(m³/h) 48K Curve for120Pa ESP 1500 1700 1900 2100 2300 2500 Air Flow(m³/h) UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 63
& & 60K 60K Curve for 80Pa ESP 1500 1700 1900 2100 2300 2500 Air Flow(m³/h) 60K Curve for120Pa ESP 1500 1700 1900 2100 2300 2500 Air Flow(m³/h) UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
5-3. Dip Switch Setting 18K(INDOOR ) 24K,36K,48K,60K(OUTDOOR) ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 84
5-5. System Parameter Adjustment Internal control parameter adjustment can be performed. OPERATION: ①Hold down both“MODE”button and“ADD.FUNC.”button for 3 seconds, symbol and parameter number blinking at the same time. ②Press“ ”“ ”button to adjust parameter number until display “17”. And press “ENTER”button to entering system parameter adaption state, symbol stop blinking.
Page 85
Parameter code will not display if the indoor unit is not equipped with this function. Please refer to indoor unit manual to check whether this function is effective. EXIT: Press "ON/OFF" button to exit, or no operation within 30 seconds automatically exit. ...
5-4 Static Pressure Setting(only for duct type) CHANGE OF STATIC PRESSURE The static pressure outside the indoor unit can be chosen . You can change the static pressure by changing the fan motor terminal which refer to following Fig.below: ON/OFF UNITARY AIR CONDITIONER TECHNICAL&...
5-6. Sensor parameter THE PARAMETER OF OUTDOOR COMPRESSOR DISCHARGE TEMPERATURE SENSOR: (R =187.25K±6.3%;R =3.77K±2.5K;B0/100=3979K±1%) THE PARAMETER OF THE OTHER SENSOR IN INDOOR AND OUTDOOR UNIT: T [ ℃ ] DR(MIN)% DR(MAX)% Rmin [ KΩ ] Rnom [ KΩ ] Rmax [ KΩ ] 7.47 908.2603 985.5274...
6-1 Indoor control mode 1.Major general technical parameters 1 Remote receiver distance: 8 m. 2 Remote receiver angle: Less than 80 degrees. 3 Temperature control accuracy: ±1℃. 4 Time error: Less than 1%. 2. Functions of the controller Control function 2.1 Emergency switch Press the emergency button can realize the starting or closing Machine, starting up according to the automatic mode of operation(invalid for duct type air-conditioner)...
Page 96
will start in the timer off condition. When the set time is up, the air conditioner will turn off after receiving a signal from the remote controller. If the air conditioner has not received a signal from the remote controller when the set time is up, it will turn off automatically. 3.
Page 97
The heating mode, remote shutdown, such as indoor heat exchanger temperature is higher, the wind blowing out opportunities continue to run the waste heat. Cool and dehumidification mode , after the compressor close, indoor machine will continue to set the speed of operation for a period of time. 2.9 automatically model This model does not automatically model function, emergency button cannot set the automatic mode of operation, can use the emergency switch shutdown, remote setting the...
6-2 Outdoor mode control Control function 1.Cooling Anti-freeze Protection To prevent indoor air conditioner evaporator temperature is too low, the indoor coil sensor for real time detection of evaporator. If the indoor coil temperature is too low, the compressor will protect. 2.
Page 99
To prevent compressor from restart frequently in the condition that system pressure has not been completely balanced, it can’t be restarted within 3 minutes. 7. Pressure Protection: When the pressure increases to a preset value, the pressure switch will automatically protect. Compressor will stop and report the fault code protection. ON/OFF UNITARY AIR CONDITIONER TECHNICAL&...
Trouble guide When the air conditioner failure occurs, the fault code will displays on control board , wire remote controller or display panel. HOW TO CHECK FAULT CODES INDOOR UNIT 1.WALL MOUNTED TYPE For Free-match series Run the air-conditioner by wireless remote controller , continue pressing “SLEEP ”button for 4 times, fault codes will flashing rapidly on the...
Page 101
MOEDL:YXE-C01U FIG.2 ERROR CODE DISPLAY ON WIRE REMOT CONTROLLER (2)CHECK ERROR CODES BY DISPLAY PANEL(CASSETTE type and CEILING &FLOOR type) Display by lamp indicator Lamp RUN(LED2 ,red) and Lamp DEFROST(LED5 ,green)flashing,Lamp RUN display fault code ten digit number, lamp DEFROST display fault code single digit number (as shown fig. below). For example,fault code 36:...
Page 102
ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 103
LED FALSH CONTROL:flash 300mS(T1),off 300mS(T2),after 2000mS(T3)fault code repeat displays. (as shown below) T1 T2 Fig.2 LED FALSH CONTROL 3.Duct type indoor units of VRF---FAULT CODE DISPLAY BY INDOOR BOARD LED2 and LED5 are failure indicate lamps, LED2(RED) indicate fault code ten digit number, LED5(GREEN) indicate single digit number code ON/OFF UNITARY AIR CONDITIONER TECHNICAL&...
Page 104
2.OUTDOOR UNIT FAULT CODE DISPLAY (1) ON/OFF UNITARY TYPE(with outdoor control box) Fault code display by indicate lamps of outdoor control board flash. The times that the lamp flashes equal to fault code. LED2-fault code lamp LED FALSH CONTROL: flash 300mS(T1), off 300mS(T2), after 900mS(T3)fault code repeat displays. (as shown below) T1 T2 (2)INVERTER UNITARY AIR CONDITONER , MULTI-SPLIT TYPE AIR CONDITONER&VRF:...
Page 105
Outdoor Control Board Digital Tube FOR INVERTER UNITARY AIR CONDITONER&VRF * VRF: Indoor unit can indicate both indoor failure and outdoor failure ,but outdoor only indicate outdoor’s. FOR MULTI-SPLIT TYPE Error code display on digital tube board directly. ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 106
3.Fault code display ( Driver Board ) The lamp of driver board flash shows failure occur. Or, fault code can be check on digital tube board . ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 107
The following is the fault code table of outdoor. sheet 1 Outdoor Error Code Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1.Reconnect the outdoor ambient 1.The outdoor ambient temperature sensor temperature sensor; connect loose; Outdoor ambient temperature 2.Replace the outdoor ambient 2.The outdoor ambient temperature sensor is...
Page 108
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code Applied to 1.Replace outdoor ambient ON/OFF 1.Outdoor ambient temperature sensor fault; temperature sensor; air-condition Motor blockage protection 2. Outdoor coil temperature sensor fault; 2.Replace outdoor coil temperature ers with 2 3.Outdoor control board fault.
Page 109
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 3.Replace the outdoor control board supply models Application 1. Normally protection 1.Three-phase power is abnormal; 2. Check the wiring connection refer to three-phase voltage absent phase 2.The outdoor wiring connect wrong; the wiring diagram;...
Page 110
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1.Reconnect the wiring of the suction 1.The wiring of the suction temperature temperature sensor; Suction temperature sensor sensor connect loose; 2.Replace the suction temperature fault 2. The suction temperature sensor is failure; sensor;...
Page 111
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 2.The sensor of the expansion valve A(thick 2. Replace the sensor for the &inverter tube)is failure; expansion valve A(thick tube); unitary types 3.The sampling circuit is abnormally 3.
Page 112
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 2.The high-pressure pressure sensor is 2.Replace the high-pressure pressure failure sensor; 3.The sampling circuit of the high-pressure 3.Replace the outdoor control board. pressure sensor is failure 1.The wiring of the low-pressure pressure 1.Reconnect the wiring of the sensor connect loose;...
Page 113
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code as capillary, expansion valve) 4. Normally protection. 1.Reconnect the wiring of the up DC 1.The wiring of the up DC fan motor connect fan motor; loose; 2.Replace the up DC fan motor; 2.
Page 114
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The wiring of the sensor connect loose; 1. Reconnect the wiring of the sensor; Expansion valve E 2.The sensor of the expansion valve Eis 2. Replace the sensor for the FOR Branch temperature sensor fault failure;...
Page 115
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code the refrigerant of the unit is not Discharge the refrigerant and charge The refrigerant of the unit is not enough enough fault the refrigerant refer to the rating label 1.The wiring of the 4-way valve coil connect 1.
Page 116
The following is the fault code table of indoor. Sheet 2 Indoor Error Code List Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The buttons are failure; 1. Replace the display board; 2. The cable of the display board is 2.
Page 117
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The connection cable between the indoor unit and the outdoor unit connect 1. Reconnect the connection cable wrong; refer to the indoor and outdoor 2.The communication cable between wiring diagram;...
Page 118
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. Check whether there are something to block the drain hose or the height of the drain hose is too 1. The water level of the drain pan high;...
Page 119
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 4.Indoor control board is failure. 1. The cable of the water tank water temperature sensor 2 connect loose; 1. Reconnect the cable of the water 2. The cable of the water tank water temperature sensor 2;...
Page 120
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code indoor unit and the outdoor unit is wiring diagram; failure or 4. Replace the indoor control board; the cable between the indoor control 5. Replace the outdoor control board. board to terminal is failure or the cable between...
Page 121
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The cable of the room temperature 1.Reconnect the cable of the room sensor connect loose; temperature sensor; Indoor ambient 2. The room temperature sensor is 2. Replace the room temperature Temperature Sensor Fault failure;...
Page 122
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The cable of the temperature sensor 1. Reconnect the able of the temperature sensor of the outlet of The outlet of water the outlet of water side is failure; water side;...
Page 123
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1.The wiring between the display board to 1. Reconnect the between the display the indoor control board connect loose; board to the indoor control board; 2.The sequence of the wiring between 2.
Page 124
The expansion valve or the capillary is failure Replace the expansion valve or the capillary Note 4:Over load in heating mode Overload in heating mode The root cause Corrective measure Discharge the refrigerant, and recharge the refrigerant refer to the The refrigerant is excessive rating label The indoor ambient temperature is too high...
Page 125
The following is the fault code table of driver board. Analysis of the Driving Board Fault (Except Free-match 20K&16K DUAL TYPES), Driver board fault codes trouble shooting details see sheet 5. I. Driver fault code display by indicate lamps of driver board flashing. The times that the lamp flashes equal to fault code.
Page 126
Fault Fault Description Possible Reason of Abnormality How to Deal With code Communication between 1,Communication wire connect not well; 1, Check compressor wire connect. driver board and control 2,Driver board fault; 2,Change the driver board; board fault 3,Control board fault; 3,Change the control board ;...
Page 127
1 time flash 1 time flash LED ON LED ON LED OFF LED OFF 1.0sec 1.0sec 0.5sec 0.5sec For example,fault code 4: Indicator light flash 4 times1-second short LED on/off Intervals for a period of time again, reports No. 4 fault. LED ON LED OFF 3.0sec...
Page 128
Fault Fault Description Possible Reason of Abnormality How to Deal With code 2、 Driver board failure; board; 3、PFC failure; 3、Change the PFC. DC voltage detected abnormal . 1、 Input voltage is too high or 1,Check the power supply. too low; PFC LOW voltage detected failure.
Page 129
8-1. Check refrigerant system TEST SYSTEM FLOW Conditions: ① Compressor is running. ② The air condition should be installed in good ventilation. Tool: Pressure Gauge Technique: ① see ② feel ③ test ----- Tube defrost. FEEL ----- The difference between tube’s temperature. TEST ----- Test pressure.
Page 130
Test system flow Cooling mode Test system The pressure on the pressure.Does the low high side. pressure normal at service part ? Recharge refrigerant after air purging with If the pressure is The pressure on the the vacuum close to static low side.
Page 131
8-2.Check parts unit 1. INDOOR FAN MOTOR MOTOR EXAMINE AND REPAIR Circuit diagram: DUCT TYPE YSK95-45-4-B M1:138Ω A1:42.5Ω A2:22Ω A3:17.6Ω A4:14.6Ω A5:81.4Ω BROWN-BLUE:70.1 BROWN-ORANGE:75.5 BROWN-RED:10.3 RAD –WHITE:11.4 WHITE-BLACK:16.1 Y7S423B814 UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 132
BLUE- BROWN:52.5 BROWN-RED:3.78 RAD –YELLOW:3.68 YELLOW–WHITE:0.89 WHITE-BLACK:4.67 ORANGE- BROWN:29.5 48K,60K Y7S423C237 BLUE- BROWN:17.89 ORANGE1- BROWN:27.2 BROWN-RED:3.35 RAD –WHITE:4.77 WHITE-BLACK:2.72 UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 133
CASSETTE TYPE M:240Ω A1:60Ω A2:33Ω A3:143Ω M:209.4Ω A1:36.2Ω A2:51.5Ω A3:109.2Ω YDK75-8-2 M:75Ω A:97.5Ω UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 134
48K&60K YDK80-8-2 M:75Ω A:97.5Ω UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 135
Ceiling&Floor type MOTOR EXAMINE AND REPAIR Circuit diagram: YSK110-22-4-A M: 187Ω A1:37.5Ω A2:27.8Ω A3:146Ω YSK110-100-4-A M:55 Ω A1:23.2 Ω A2:10.9Ω A3:18.3Ω Y7S423B212 UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 136
WHITE-BLACK:41.49 BLACK-BLUE:13.25 BLUE-YELLOW:12.39 RED-BLACK:35.21 48K&60K Y7S423C032 WHITE-BLACK:42.69 BLACK-BLUE:9.19 BLUE-YELLOW:9.09 RED-BLACK:36.41 Test in resistance. TOOL: Multimeter. Test the resistance of the main winding. The indoor fan motor is fault if the resistance of main winding 0(short circuit)or∞(open circuit). Test in voltage TOOL: Multimeter.
Page 137
Notes: 1) Please don’t hold motor by lead wires. 2) Please don’t plug IN/OUT the motor connecter while power ON. Please don’t drop hurl or dump motor against hard material. Malfunction may not be observed at early stage after such shock. But it may be found later, this type of mishandling void our warranty.
Page 138
2. OUTDOOR FAN MOTOR MOTOR EXAMINE AND REPAIR Circuit diagram YDK29-6I-25 Winding resistance ( at 20℃) M: 231Ω A: 168Ω YDK70-6H-3: WINDING BROWN " " M The main winding BLACK " " A The auxiliary winding Capacitor ℃ Hot protector 130 WHITE YELLOW BLUE...
Page 139
YDK29-6I-39 YDK29-6I-41 Winding resistance ( at 20℃) M:187Ω±15% A:BLUE-RED-WHITE-YELLOW 50/21/106Ω±15% YDK65-6-9024、YDK65-6-9061 Winding resistance ( at 20℃) M:83.0Ω A1:23.4Ω A2:14.0Ω A3: 63.5Ω UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 140
Test in resistance. TOOL: Multimeter. Test the resistance of the main winding. The outdoor fan motor is fault if the resistance of main winding 0(short circuit)or∞(open circuit). Notes: 1) Please don’t hold motor by lead wires. 2) Please don’t plug IN/OUT the motor connecter while power ON. 3)...
Page 141
3. COMPRESSOR COMPRESSOR EXAMINE AND REPAIR PA190M2CS-4KTL PA290G2CS-4MUL1 C-SBN303H8D UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 142
ATE550SC3Q9RK C-SBN453H8D Test in resistance. TOOL: Multimeter. Test the resistance of the winding. The compressor is fault if the resistance of winding 0(short circuit)or∞(open circuit) Familiar error: UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V5.0...
Page 143
1)Compressor motor lock. 2)Discharge pressure value approaches static pressure value . 3)Compressor motor winding abnormality. Notes: 1)Don’t put a compressor on its side or turn over. 2) Please assembly the compressor in your air conditioner rapidly after removing the plugs. Don’t place the comp.
Page 144
Fuse Fig.2 7.CAPACITOR 1) Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig.3. 2) Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value. * The capacitor is “good”...