Design Parameters - Quantech QTC2015T Manual

Air-cooled scroll chillers 15 – 46 ton, 53-162 kw, 60 hz, r-410a
Table of Contents

Advertisement

Design Parameters

QUANTECH
LEAVING WATER
MODEL
TEMPERATURE (°F)
MIN
015T
40
020T
40
025T
40
030T
40
035T
40
040T
40
045T
40
LEAVING WATER
MODEL
TEMPERATURE (°C)
MIN
015T
4.4
020T
4.4
025T
4.4
030T
4.4
035T
4.4
040T
4.4
045T
4.4
NoTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Quantech Sales Office for ap-
plication requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Quantech Sales Office for
application guidelines.
3. The evaporator is protected against freezing to -20°f (-28.8°C) with an electric heater as standard.
4. for operation at temperatures below 25°f (-3.9°C), the optional low Ambient Kit will need to be installed
on the system (for QTC2040T-045T models only).
5. for operation at temperatures above 115°f (46.1°C), the optional high Ambient Kit will need to be in-
stalled on the system.
QTC2 ENGLISH
COOLER
FLOW (GPM)
MAX
MIN
MAX
55
10
55
10
55
10
55
10
55
40
55
40
55
60
QTC2 SI UNITS
COOLER
FLOW (L/S)
MAX
MIN
MAX
12.8
0.6
12.8
0.6
12.8
0.6
12.8
0.6
12.8
2.5
12.8
2.5
12.8
3.8
FORM QTC2-eg1 (515)
AIR ON
CONDENSER (°F)
MIN
MAX
150
0
150
0
150
0
150
0
200
0
200
0
300
0
AIR ON
CONDENSER (°C)
MIN
MAX
9.5
-17.7
9.5
-17.7
9.5
-17.7
9.5
-17.7
12.6
-17.7
12.6
-17.7
18.9
-17.7
125
125
125
125
125
125
125
51.7
51.7
51.7
51.7
51.7
51.7
51.7
13