Air-cooled scroll chillers 15 – 46 ton, 53-162 kw, 60 hz, r-410a
Table of Contents

Advertisement

FORM QTC2-eg1 (515)
Unit Dimensions - English (Cont'd)
2 1/4"
TO ACCESS PANEL 16 1/4"
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
22
QTC2020T
3 1/4"
6 3/4"
3 15/16"
46 1/16"
B
45 1/4"
11 5/8"
12 13/16"
8 5/16"
2" ANSI/AWWA C-606
CONN (typ)
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
7/8" TYP.
VIEW B-B
BOTTOM OF PANEL
IN
2" DIA
(2) 3.0 X 1.50
OUT
B
RIGGING HOLES
BOTH ENDS
11"
12 13/16"
8 5/16"
18 3/4"
44 5/16"
BASE WIDTH
LEFT END
LD18671
QUANTECH