Quantech QTC2015T Manual page 44

Air-cooled scroll chillers 15 – 46 ton, 53-162 kw, 60 hz, r-410a
Table of Contents

Advertisement

FORM QTC2-eg1 (515)
Unit Dimensions - Metric (Cont'd)
1213
1192
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cutouts; however,
the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m; rear to wall –
2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one
adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 152mm.
44
QTC2040T
171
82
22 TYP.
100
VIEW B-B
BOTTOM OF PANEL
76 VICTAULIC (typ)
LIQUID OUT
2292 BASE WIDTH
LEFT END
LIQUID IN
ELECTRICAL ACCESS
PANEL
250
401
321
1146
LD18699
640
QUANTECH