Huawei SmartACU2000B Quick Manual page 8

Smart array controller with no pid module, 800 v ac
Hide thumbs Also See for SmartACU2000B:
Table of Contents

Advertisement

The following table describes the cables to be prepared by yourself in the fiber ring networking scenario.
No. Cable
Three-phase AC
1
power cable
Peripheral
2
network cable
Peripheral
RS485
3
communications
cable
Cabinet PE
4
cable
5
Optical cable
Single-phase AC
6
power cable
24 V DC input
7
and output
power cables
Recommended Model or Specifications
Three-core (L1, L2, and L3) outdoor copper
armored cable with three OT-M6 terminals (L1,
L2, and L3)
When the rated AC voltage on the low-voltage
side of the box-type transformer is less than or
equal to 500 V, the operating voltage between
the three-phase AC power cable and the
ground should be greater than or equal to 600
V.
When the rated AC voltage on the low-voltage
side of the box-type transformer is greater than
500 V and less than or equal to 800 V, the
operating voltage between the three-phase AC
power cable and the ground should be greater
than or equal to 1000 V.
CAT 5E outdoor shielded network cable with an
outer diameter less than 9 mm (0.35 in.) and
internal resistance not greater than 1.5 ohms/10 m
(1.5 ohms/393.70 in.), as well as a shielded RJ45
connector
A computer cable (DJYP2VP2-22 2x2x1) or
armored shielded twisted pair that can be used
outdoors and OT-M4 terminals
Outdoor copper cable with an OT-M6 terminal
Four-core or eight-core single-mode armored
optical cable with a transmission wavelength of
1310 nm and an outer diameter less than or equal
to 18 mm (0.71 in.)
Common connection: one two-core outdoor
copper armored cable
Connection through a tube: two single-core
outdoor copper cables
Operating voltage to the ground ≥ 300 V
Common connection: one two-core outdoor
copper armored cable
Connection through a tube: two single-core
outdoor copper cables
Operating voltage to the ground ≥ 300 V
7
Cross-sectional Area
Range of the Cable
(Recommended)
2
8–10 mm
(10 mm
8 AWG
N/A
2
2
0.5–1 mm
(1 mm
20–18 AWG (18 AWG)
2
6–16 mm
(16 mm
10–6 AWG (6 AWG)
N/A
2
2
4–6 mm
(4 mm
)
12–10 AWG (12 AWG)
2
2.5–4 mm
(2.5 mm
14–12 AWG (14 AWG)
2
)
)
2
)
2
)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents