Laars MagnaTherm MGH1600 Installation And Operation Instructions For page 97

Modulating boiler/water heater, 1,600/1,999/2,499/3,000/3,500/4,000 mbtu/h
Table of Contents

Advertisement

MagnaTherm Boilers and Water Heaters
122
Lightoff rate proving failed
123
Purge rate proving failed
128
Fan speed failed during prepurge
129
Fan speed failed during preignition
130
Fan speed failed during ignition
131
Fan movement detected during standby
132
Fan speed failed during run
137
ILK (Interlock) failed to close
L
1. Check wiring and correct any potential wiring
errors.
2. Check VFD's (Variable-speed Fan Drive) ability
to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
L
1. Check wiring and correct any potential wiring
errors.
2. Check VFD's (Variable-speed Fan Drive) ability
to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H or L
1. Check wiring and correct any potential wiring
errors.
2. Check the VFDs (Variable-speed Fan Drive)
ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H or L
1. Check wiring and correct any potential wiring
errors.
2. Check the VFDs (Variable-speed Fan Drive)
ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H or L
1. Check wiring and correct any potential wiring
errors.
2. Check the VFDs (Variable-speed Fan Drive)
ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H
1. Check wiring and correct any potential wiring
errors.
2. Check the VFDs (Variable-speed Fan Drive)
ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H
1. Check wiring and correct any potential wiring
errors.
2. Check the VFDs (Variable-speed Fan Drive)
ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper
function.
3. Verify voltage through the interlock string to the
interlock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
Page 93

Advertisement

Table of Contents
loading

Table of Contents