Laars MagnaTherm MGH1600 Installation And Operation Instructions For page 83

Modulating boiler/water heater, 1,600/1,999/2,499/3,000/3,500/4,000 mbtu/h
Table of Contents

Advertisement

MagnaTherm Boilers and Water Heaters
Model
Gas Type
Natural
1,600
Propane
Natural
2,000
Propane
Natural
2,500
Propane
Natural
3,000
Propane
Natural
3,500
Propane
Natural
4,000
Propane
* - Only check the pressures if there are problems getting the CO
Table 24. CO
RangeandPressureDifferential
2
Gas Valve
High fire adjustment
Low fire adjustment
Figure 46.
High and Low Fire Adjustments on the Gas Valve
High Fire CO
Low Fire CO
2
9.0% ± 0.2
.25 lower than high fire CO
10.0% ± 0.2
.25 lower than high fire CO
9.0% ± 0.2
.25 lower than high fire CO
10.0% ± 0.2
.25 lower than high fire CO
9.0% ± 0.2
.25 lower than high fire CO
10.0% ± 0.2
.25 lower than high fire CO
9.0% ± 0.2
.25 lower than high fire CO
10.0% ± 0.2
.25 lower than high fire CO
9.0% ± 0.2
.25 lower than high fire CO
10.0% ± 0.2
.25 lower than high fire CO
9.0% ± 0.2
.25 lower than high fire CO
10.0% ± 0.2
.25 lower than high fire CO
Pressure Differential
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.9" to .09" wc
2
0.9" to .09" wc
2
0.5" to 1.2" wc
2
0.5" to 1.2" wc
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
and CO values in range.
2
Page 79
Shown is a model 3000.
All units have a similar
design with the gas valve
similarly located.