Laars MagnaTherm MGH1600 Installation And Operation Instructions For page 94

Modulating boiler/water heater, 1,600/1,999/2,499/3,000/3,500/4,000 mbtu/h
Table of Contents

Advertisement

Page 90
50
Modulation fault
51
Pump fault
52
Motor tachometer fault
53
AC input phases reversed
59
Internal Fault: Mux pin shorted
61
Anti short cycle
62
Fan speed not proved
63
Rollout switch, is regarding the
SAFETY DEVICES (OFF)
To diagnose, test all of the following:
Flow Switch
Additional High Limit (Field Supplied)
Low Water Cut Off
Low pressure gas switch – Inlet Side of
Gas Valve
High Pressure gas switch – Outlet Side
of Gas Valve
Condensate Level Switch
64
PII (Pre-Ignition Interlock) OFF
67
ILK (Interlock) OFF
68
ILK (Interlock) ON
70
Wait for leakage test completion
78
Demand Lost in Run
H
Internal sub-system fault.
H
1. Review alert messages for possible trends.
H
2. Correct possible problems.
L
1. Check the module and display connections.
2. Check the module power supply and make
sure that both frequency and voltage meet the
specifications.
3. On 24 VAC applications, assure that J4 terminal
10 and J8 terminal 2 are connected together.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
H
Will not be a lockout fault. Hold Only.
H
H
1. Reset the low gas pressure valve and the high
gas pressure valve.
2. Check for power at all Safety Components.
3. Check wiring and correct any faults.
4. Check all safety interlocks connected to the
safety circuit to assure proper function.
5. If code persists, contact Tech Support.
H or L
1. Check wiring and correct any faults.
2. Check Preignition Interlock switches to assure
proper functioning.
3. Check the valve operation.
4. Reset and sequence the module; monitor the
PII status.
5. If code persists, replace the module.
H or L
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper
function.
3. Verify voltage through the interlock string to the
H or L
interlock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
H
1. Internal Fault. Reset module.
2. If fault repeats, replace module.
H
1. Check wiring and correct any possible errors.
2. If previous steps are correct and fault persists,
replace the module.
LAARS Heating Systems