Laars MagnaTherm MGH1600 Installation And Operation Instructions For page 93

Modulating boiler/water heater, 1,600/1,999/2,499/3,000/3,500/4,000 mbtu/h
Table of Contents

Advertisement

MagnaTherm Boilers and Water Heaters
16
Internal fault:
Safety relay test failed due to safety
relay OFF
17
Internal fault:
Safety relay test failed due to safety
relay not OFF
18
Internal fault:
Safety relay test failed due to feedback
not ON
19
Internal fault:
Safety RAM write
20
Internal fault:
Internal fault: Flame ripple and overflow
21
Internal fault:
Flame number of sample mismatch
22
Internal fault:
Flame bias out of range
23
Internal fault:
Bias changed since heating cycle starts
24
Internal fault:
Spark voltage stuck low or high
25
Internal fault:
Spark voltage changed too much during
flame sensing time
26
Internal fault:
Static flame ripple
27
Internal fault:
Flame rod shorted to ground detected
28
Internal fault:
A/D linearity test fails
29
Internal fault:
Flame bias cannot be set in range
30
Internal fault:
Flame bias shorted to adjacent pin
31
Internal fault:
SLO electronics unknown error
32-46 Internal fault:
Safety Key 0 through 14
47
Flame Rod to ground leakage
48
Static flame (not flickering)
49
24 VAC voltage low/high
L
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
L
L
H
H
H
H
H
H
H
H
H
H
H
H
L
H
H
H
1. Check the module and display connections.
2. Check the module power supply and make
sure that frequency, voltage and VA meet the
specifications.
Page 89