Vertiv Liebert LDMF User Manual
Vertiv Liebert LDMF User Manual

Vertiv Liebert LDMF User Manual

Distribution monitoring
Table of Contents

Advertisement

Liebert®
LDMF™ Distribution Monitoring
User Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Liebert LDMF and is the answer not in the manual?

Questions and answers

Summary of Contents for Vertiv Liebert LDMF

  • Page 1 Liebert® LDMF™ Distribution Monitoring User Manual...
  • Page 2 The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
  • Page 3: Table Of Contents

    Mode Buttons ................23 Vertiv...
  • Page 4 Edit the Liebert LDMF Unit Properties ........
  • Page 5: Important Safety Instructions

    Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense. Liebert LDMF as a functional component of a power distribution and supply product complies with the requirements of EMC Directive 2004/108/EC and the published technical standards.
  • Page 6: Glossary Of Abbreviations

    LDMF4 Cabinets) PM4 Adapter Board Power Conditioning and Distribution Power Distribution Unit Power Monitoring 4th Generation PM4 Interface Board PLIB PM4 Large Interface Board PM4 Monitoring Board Service Terminal Port | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 7: Product Overview

    Liebert SiteLink interface. ® The Liebert LDMF consists of a monitor board, interface board, optional local display and Branch Sensor Modules (BSM). The Liebert LDMF is capable of receiving input from current branch sensor modules. The sensor module (BSM) contains 100A current transformers (CTs) encapsulated in an epoxy-filled plastic enclosure designed to be mounted next to the panelboard.
  • Page 8: Major Components

    • A DB9 serial port on the outside panel is available for local configuration. PM4 Interface Board (PIB) The Liebert LDMF PM4 Interface Board (PIB) provides connections for the voltage and currents of the panelboard main circuit breaker as well as the CT current for any installed large branches or subfeed breakers (maximum of 18 CTs).
  • Page 9: Pm4 Large Interface Board (Plib)

    1A secondary CT will damage the PIB and the CT. To ensure the proper current ratio and accuracy, the CTs should be purchased through Vertiv. See Table 1 for details. Contact your local Vertiv representative or call Vertiv Support at 800-543-2378.
  • Page 10 Connecting anything other than a 1A secondary CT will damage the PLIB and the CT. To ensure the proper current ratio and accuracy, the CTs should be purchased through Vertiv. See Table 1 for details. Contact your local Vertiv representative or call Vertiv Support at 800-543-2378.
  • Page 11: Branch Circuit Monitoring Sensor Module (Bsm)

    PMB will still have power to ® communicate alarms via the local display or remotely via Liebert IntelliSlot cards. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 12: Human-Machine Interface/Display Assembly (Optional)

    LDMF Configuration software, which is available for download at the Liebert Web site. Refer to 5.3 - Downloading the Software for downloading instructions and see 5.5 - Using the Configuration Tool for details on using the software. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 13: Pm4 Adapter Board

    LDMF summary alarm contacts. • If two Liebert LDMF systems are provided, the two PABs are connected to each other at the factory. It is only necessary to connect to one PAB to monitor the Customer Summary Alarm; the two Liebert LDMF units share summary alarm contacts.
  • Page 14: Installation

    Off and locked-out in accordance with NEC and local/state code. NOTE Liebert LDMF components and any other monitoring devices should be installed only by properly trained and qualified personnel. This section provides instructions for installing and connecting Liebert LDMF current transformers.
  • Page 15: Installing A Solid-Core Current Transformer

    To configure the branch circuits, refer to 5.5.11 - Add a Circuit Breaker. NOTE • Panelboard A is either Panelboard 1 or Panelboard 3. • Panelboard B is either Panelboard 2 or Panelboard 4 depending on which Liebert LDMF Control Board is being configured. Installing a Solid-Core Current Transformer WARNING A solid-core CT cannot be installed on a wire while current is flowing through the wire.
  • Page 16: Installing A Current Transformer On The Pib Interface Board

    If the Power Distribution Center is supplied with optional isolated ground, the isolated ground circuit can be monitored by the Liebert LDMF. Usually the CT is already installed and wired to the Large Branch Terminal Block at the factory. If not, perform the following steps: (For Isolated Ground CT Installation only) •...
  • Page 17: Table 2 Large Branch Breaker Ct Wiring

    If a second subfeed or large branch breaker will be installed, the same pattern will continue. Pins 11 and 12 will be Phase A CT for the second breaker, Pins 13 and 14 will be Phase B CT and so on. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 18: Table

    • • Wire Color Connector P3 (A) LB12 LB11 Phase Position • • • • • • • • • Wire Color Connector P4 (B) LB13 LB12 LB11 LB10 Phase | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 19: Table

    A = A Phase CT N = Neutral CT B = Black LB = Large Branch Breaker CT B = B Phase CT G = Ground CT C = C Phase CT | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 20: Connecting A Current Transformer To The Pm4 Large Interface Board (Plib)

    • Connect the Ground CT for the second breaker to CT36 (white wire to CT36+, black to CT36-). • Continue the same pattern until all CT connections are used or there are no more outputs or subfeed CTs to add. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 21: Table 4 Ct Table For Pm4 Large Interface Board #1

    CT37 Pins Connector Wire Color Phase W = White A = A Phase N = Neutral B = Black B = B Phase G = Ground C = C Phase | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 22: Table 5 Ct Table For Pm4 Large Interface Board #2

    NONE NONE CT13 CT12 CT11 Phase W = White A = A Phase N = Neutral B = Black B = B Phase G = Ground C = C Phase | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 23: Operation

    5.0 OPERATION The Liebert LDMF is a factory-installed option to provide monitoring of the main breaker, branch circuit breakers and subfeed breakers. It may be installed in the Liebert PPC, Liebert FDC, Liebert FPC. Liebert RX and the Liebert RDC.
  • Page 24: Alarms

    Alarms The Liebert LDMF constantly monitors electrical data for each breaker and subfeed. When the unit detects an alarm condition, it annunciates and displays alarm messages via the Monitor program (see 5.4 - Using the Monitor Tool (Used Only for Startup and Diagnostics)) as well as showing the alarm on the local display (if installed).
  • Page 25 Detects and annunciates upon occurrence of Summary Alarm — — — any alarm Detects and annunciates upon occurrence of Panelboard Summary Alarm — — — branch or panelboard main breaker alarm | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 26: Communication

    Communication Connecting locally to the Liebert LDMF Monitoring option requires a female-to-female (F-F) DB9 null modem cable. There will be an external port on the Liebert Power product labeled LDMF SETUP. Connect the DB9 null modem cable to a local PC. Once connected you may run any of the provided software tools that can be downloaded from the Liebert Web site (see 5.3 -...
  • Page 27: Figure 1 Rs-232 Port

    Figure 1 RS-232 port RS-232 Port | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 28: Downloading The Software

    Downloading the Software The Liebert LDMF has three software tools for monitoring, configuration and firmware updates: • Monitoring - see 5.4 - Using the Monitor Tool (Used Only for Startup and Diagnostics) • Configuration - see 5.5 - Using the Configuration Tool These programs may be downloaded at no charge or license fee at the Liebert Web site,www.vertivco.com.
  • Page 29: Monitor Menu Options

    Clears all latched alarms for the selected panel. Any alarm condition that is still active is latched again after the hysteresis interval passes. Help Menu • About Displays information about Liebert Distribution Monitoring. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 30: Panel Status And Real-Time Clock

    The Real-Time Clock displays the time as stored in the Liebert LDMF unit. The time will not display correctly if the time zone is incorrect in the PC. If the time displayed is incorrect and the problem is not caused by a time-zone configuration problem: •...
  • Page 31: Mode Buttons

    (see 5.3 - Downloading the Software). Ensure the existing configuration file is saved locally before making any modifications. Please contact your local Vertiv representative or call Vertiv Support at 800-543-2378 for assistance. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 32: Starting The Configuration Program

    Work Offline Proceed to 5.5.2 - Main Configuration Window Overview to begin configuration. When a local connection to the Liebert LDMF can be performed, load the configuration using the instructions in 5.5.3 - Load a Configuration File from Disk. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 33: Main Configuration Window Overview

    • Load from File This feature may be used to install a backup copy of a Disk configuration file or set up a new Liebert LDMF installation. Uploads the current configuration from the PC to the Liebert LDMF after making changes to the configuration.
  • Page 34: Load A Configuration File From Disk

    Once the rebooting process is complete, the configuration is active. NOTE Configuration changes are not stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv...
  • Page 35: Save The Configuration File To Disk

    Click Save. 5.5.6 Select Panel to View Up to two panelboards may be connected to the Liebert LDMF (see 4.1.1 - Connecting Panelboards A and B). Each may be viewed in the Configuration main window. To switch the view to a different panel: Save to File •...
  • Page 36: Edit The Liebert Ldmf Unit Properties

    • When finished, click Install to Unit to upload the changes to the Liebert LDMF. NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 37: Edit The Breaker Properties

    (click to save changes to Liebert LDMF) To view or change parameters and alarm settings of a breaker: • Click on the breaker in the left pane. When selected, the breaker has a yellow outline. • Refer to Table 11 to make changes:...
  • Page 38 NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 39: Add A Circuit Breaker

    Program. Once connected, the configuration file that is currently programmed will be displayed. NOTE Vertiv highly recommends saving the configuration file to the local PC as a backup before making any changes to the configuration file. Perform the steps outlined in 5.5.5 - Save the Configuration File to Disk before proceeding.
  • Page 40 • When finished, click Install to Unit to upload the changes to the Liebert LDMF. NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 41: Adding A Subfeed Breaker

    Click on the Add Subfeed button to return to the main Configuration window. • In the Breaker Properties box of the Configuration window, change the subfeed breaker’s name, parameters and alarm setpoints as needed (see 5.5.10 - Edit the Breaker Properties). | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 42: Delete A Circuit Breaker/Subfeed Breaker

    • When finished, click Install to Unit to upload the changes to the Liebert LDMF. NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. 5.5.13 Delete a Circuit Breaker/Subfeed Breaker Removing a breaker from the configuration is required after moving or removing circuit breakers in the panelboard.
  • Page 43: Upgrading The Firmware

    To upgrade the firmware: Make sure the Liebert LDMF unit is powered ON. 2. Connect the PC to the Liebert LDMF via the external DB9 connection. Refer to 5.2.1 - LDMF Setup Port Connection. Run the file named Flash-x.x.x.exe (where x.x.x is the version number).
  • Page 44 Start Scan Button 6. If the Liebert LDMF unit is detected, a confirmation window appears. Click Yes to continue and proceed to Step 7. If the Liebert LDMF unit is NOT detected, an error message appears. Click OK to return to the Upgrade Firmware window.
  • Page 45 Browse to the folder where the Flash files are located—this should be the same folder where the Flash program was installed. • Select the file you want to download. • Click the Open button. Image File button Navigate to File | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 46 In the Summary Status box, the Number of Units should be 0 under Failed (above right). • In the Detail Status box, Running should appear in the Progress column—this indicates that the BCB has been restarted successfully. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 47: Display Controls (Hmi)

    • Power Indicator (Green LED) - illuminates when power has been applied to the Liebert power product. • Alarm Status Indicator (Red LED - illuminates when the Liebert LDMF detects an alarm. The audible alarm will also sound until the Silence/Reset push button is depressed. The LED will remain illuminated until the alarm condition is cleared.
  • Page 48: Liebert Ldmf Parameter Screens

    LCD Viewing Area Navigation Keys 5.7.2 Liebert LDMF Parameter Screens Three types of parameter screens may be selected from the Main Screen by pressing the soft keys labeled Next Main, Subfeeds and Branch Breakers to display the applicable information. Branch Breakers...
  • Page 49: Liebert Ldmf Alarms

    5.7.3 Liebert LDMF Alarms If any alarms are present when parameter screens are accessed with the Main, Subfeeds or Branch Breakers keys, the Alarm Screen appears, as shown in the example below. • Press F4 (Back) to view details about the alarm on the Panelboard Main screen.
  • Page 50: Liebert Ldmf Screens

    5.7.4 Liebert LDMF Screens NOTE The images below are for representation of the menu items only. The actual display including the Controls and Indicators shown in the images below may not be present. Figure 2 Main panelboard screens—examples Panelboard Main Screen...
  • Page 51: Figure 3 Subfeed Screens-Examples

    SUBFEED LABEL IX CF = X.X IX THD = XX.X IY CF = X.X IY THD = XX.X IZ CF = X.X IZ THD = XX.X NEXT SUB FD BACK HELP | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 52: Figure 4 Branch Breaker Screens-Examples

    NEXT GROUP BRANCH SELECT BACK BACK HELP HELP Branch Alarms PANEL BOARD LABEL BRANCH LABEL NO ALARMS PRESENT or OVER CURR ALRM OVER CURR WARN UNDER CURR WARN BACK HELP | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 53: Specifications

    1% for 2 - 100A 5% for 100-120A Minimum Current 200mA ENVIRONMENTAL Humidity 0-95% Temperature (Non-Operating) -68°F to 158°F (-20°C to 70°C) Temperature (Operating) 32°F to 104°F (0°C to 40°C) | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
  • Page 54: Troubleshooting / Frequently Asked Questions

    Verify the PC is connected to the LDMF Setup port and the communication cable (F-F null modem DB9) is fully seated (see 5.2.1 - LDMF Setup Port Connection). • Verify the Liebert LDMF unit has power (green LEDs on the BCB will be flashing). How can I make a backup copy of the configuration file? •...
  • Page 56 © 2018 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co.