Load meter module with remote monitoring (29 pages)
Summary of Contents for Vertiv Liebert LDMF
Page 1
Liebert® LDMF™ Distribution Monitoring User Manual...
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense. Liebert LDMF as a functional component of a power distribution and supply product complies with the requirements of EMC Directive 2004/108/EC and the published technical standards.
LDMF4 Cabinets) PM4 Adapter Board Power Conditioning and Distribution Power Distribution Unit Power Monitoring 4th Generation PM4 Interface Board PLIB PM4 Large Interface Board PM4 Monitoring Board Service Terminal Port | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Liebert SiteLink interface. ® The Liebert LDMF consists of a monitor board, interface board, optional local display and Branch Sensor Modules (BSM). The Liebert LDMF is capable of receiving input from current branch sensor modules. The sensor module (BSM) contains 100A current transformers (CTs) encapsulated in an epoxy-filled plastic enclosure designed to be mounted next to the panelboard.
• A DB9 serial port on the outside panel is available for local configuration. PM4 Interface Board (PIB) The Liebert LDMF PM4 Interface Board (PIB) provides connections for the voltage and currents of the panelboard main circuit breaker as well as the CT current for any installed large branches or subfeed breakers (maximum of 18 CTs).
1A secondary CT will damage the PIB and the CT. To ensure the proper current ratio and accuracy, the CTs should be purchased through Vertiv. See Table 1 for details. Contact your local Vertiv representative or call Vertiv Support at 800-543-2378.
Page 10
Connecting anything other than a 1A secondary CT will damage the PLIB and the CT. To ensure the proper current ratio and accuracy, the CTs should be purchased through Vertiv. See Table 1 for details. Contact your local Vertiv representative or call Vertiv Support at 800-543-2378.
PMB will still have power to ® communicate alarms via the local display or remotely via Liebert IntelliSlot cards. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
LDMF Configuration software, which is available for download at the Liebert Web site. Refer to 5.3 - Downloading the Software for downloading instructions and see 5.5 - Using the Configuration Tool for details on using the software. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
LDMF summary alarm contacts. • If two Liebert LDMF systems are provided, the two PABs are connected to each other at the factory. It is only necessary to connect to one PAB to monitor the Customer Summary Alarm; the two Liebert LDMF units share summary alarm contacts.
Off and locked-out in accordance with NEC and local/state code. NOTE Liebert LDMF components and any other monitoring devices should be installed only by properly trained and qualified personnel. This section provides instructions for installing and connecting Liebert LDMF current transformers.
To configure the branch circuits, refer to 5.5.11 - Add a Circuit Breaker. NOTE • Panelboard A is either Panelboard 1 or Panelboard 3. • Panelboard B is either Panelboard 2 or Panelboard 4 depending on which Liebert LDMF Control Board is being configured. Installing a Solid-Core Current Transformer WARNING A solid-core CT cannot be installed on a wire while current is flowing through the wire.
If the Power Distribution Center is supplied with optional isolated ground, the isolated ground circuit can be monitored by the Liebert LDMF. Usually the CT is already installed and wired to the Large Branch Terminal Block at the factory. If not, perform the following steps: (For Isolated Ground CT Installation only) •...
If a second subfeed or large branch breaker will be installed, the same pattern will continue. Pins 11 and 12 will be Phase A CT for the second breaker, Pins 13 and 14 will be Phase B CT and so on. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
A = A Phase CT N = Neutral CT B = Black LB = Large Branch Breaker CT B = B Phase CT G = Ground CT C = C Phase CT | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
• Connect the Ground CT for the second breaker to CT36 (white wire to CT36+, black to CT36-). • Continue the same pattern until all CT connections are used or there are no more outputs or subfeed CTs to add. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
CT37 Pins Connector Wire Color Phase W = White A = A Phase N = Neutral B = Black B = B Phase G = Ground C = C Phase | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
NONE NONE CT13 CT12 CT11 Phase W = White A = A Phase N = Neutral B = Black B = B Phase G = Ground C = C Phase | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
5.0 OPERATION The Liebert LDMF is a factory-installed option to provide monitoring of the main breaker, branch circuit breakers and subfeed breakers. It may be installed in the Liebert PPC, Liebert FDC, Liebert FPC. Liebert RX and the Liebert RDC.
Alarms The Liebert LDMF constantly monitors electrical data for each breaker and subfeed. When the unit detects an alarm condition, it annunciates and displays alarm messages via the Monitor program (see 5.4 - Using the Monitor Tool (Used Only for Startup and Diagnostics)) as well as showing the alarm on the local display (if installed).
Page 25
Detects and annunciates upon occurrence of Summary Alarm — — — any alarm Detects and annunciates upon occurrence of Panelboard Summary Alarm — — — branch or panelboard main breaker alarm | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Communication Connecting locally to the Liebert LDMF Monitoring option requires a female-to-female (F-F) DB9 null modem cable. There will be an external port on the Liebert Power product labeled LDMF SETUP. Connect the DB9 null modem cable to a local PC. Once connected you may run any of the provided software tools that can be downloaded from the Liebert Web site (see 5.3 -...
Downloading the Software The Liebert LDMF has three software tools for monitoring, configuration and firmware updates: • Monitoring - see 5.4 - Using the Monitor Tool (Used Only for Startup and Diagnostics) • Configuration - see 5.5 - Using the Configuration Tool These programs may be downloaded at no charge or license fee at the Liebert Web site,www.vertivco.com.
Clears all latched alarms for the selected panel. Any alarm condition that is still active is latched again after the hysteresis interval passes. Help Menu • About Displays information about Liebert Distribution Monitoring. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
The Real-Time Clock displays the time as stored in the Liebert LDMF unit. The time will not display correctly if the time zone is incorrect in the PC. If the time displayed is incorrect and the problem is not caused by a time-zone configuration problem: •...
(see 5.3 - Downloading the Software). Ensure the existing configuration file is saved locally before making any modifications. Please contact your local Vertiv representative or call Vertiv Support at 800-543-2378 for assistance. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Work Offline Proceed to 5.5.2 - Main Configuration Window Overview to begin configuration. When a local connection to the Liebert LDMF can be performed, load the configuration using the instructions in 5.5.3 - Load a Configuration File from Disk. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
• Load from File This feature may be used to install a backup copy of a Disk configuration file or set up a new Liebert LDMF installation. Uploads the current configuration from the PC to the Liebert LDMF after making changes to the configuration.
Once the rebooting process is complete, the configuration is active. NOTE Configuration changes are not stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv...
Click Save. 5.5.6 Select Panel to View Up to two panelboards may be connected to the Liebert LDMF (see 4.1.1 - Connecting Panelboards A and B). Each may be viewed in the Configuration main window. To switch the view to a different panel: Save to File •...
• When finished, click Install to Unit to upload the changes to the Liebert LDMF. NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
(click to save changes to Liebert LDMF) To view or change parameters and alarm settings of a breaker: • Click on the breaker in the left pane. When selected, the breaker has a yellow outline. • Refer to Table 11 to make changes:...
Page 38
NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Program. Once connected, the configuration file that is currently programmed will be displayed. NOTE Vertiv highly recommends saving the configuration file to the local PC as a backup before making any changes to the configuration file. Perform the steps outlined in 5.5.5 - Save the Configuration File to Disk before proceeding.
Page 40
• When finished, click Install to Unit to upload the changes to the Liebert LDMF. NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Click on the Add Subfeed button to return to the main Configuration window. • In the Breaker Properties box of the Configuration window, change the subfeed breaker’s name, parameters and alarm setpoints as needed (see 5.5.10 - Edit the Breaker Properties). | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
• When finished, click Install to Unit to upload the changes to the Liebert LDMF. NOTE The configuration changes will not be stored in the Liebert LDMF until the Install to Unit button is clicked. 5.5.13 Delete a Circuit Breaker/Subfeed Breaker Removing a breaker from the configuration is required after moving or removing circuit breakers in the panelboard.
To upgrade the firmware: Make sure the Liebert LDMF unit is powered ON. 2. Connect the PC to the Liebert LDMF via the external DB9 connection. Refer to 5.2.1 - LDMF Setup Port Connection. Run the file named Flash-x.x.x.exe (where x.x.x is the version number).
Page 44
Start Scan Button 6. If the Liebert LDMF unit is detected, a confirmation window appears. Click Yes to continue and proceed to Step 7. If the Liebert LDMF unit is NOT detected, an error message appears. Click OK to return to the Upgrade Firmware window.
Page 45
Browse to the folder where the Flash files are located—this should be the same folder where the Flash program was installed. • Select the file you want to download. • Click the Open button. Image File button Navigate to File | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Page 46
In the Summary Status box, the Number of Units should be 0 under Failed (above right). • In the Detail Status box, Running should appear in the Progress column—this indicates that the BCB has been restarted successfully. | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
• Power Indicator (Green LED) - illuminates when power has been applied to the Liebert power product. • Alarm Status Indicator (Red LED - illuminates when the Liebert LDMF detects an alarm. The audible alarm will also sound until the Silence/Reset push button is depressed. The LED will remain illuminated until the alarm condition is cleared.
LCD Viewing Area Navigation Keys 5.7.2 Liebert LDMF Parameter Screens Three types of parameter screens may be selected from the Main Screen by pressing the soft keys labeled Next Main, Subfeeds and Branch Breakers to display the applicable information. Branch Breakers...
5.7.3 Liebert LDMF Alarms If any alarms are present when parameter screens are accessed with the Main, Subfeeds or Branch Breakers keys, the Alarm Screen appears, as shown in the example below. • Press F4 (Back) to view details about the alarm on the Panelboard Main screen.
5.7.4 Liebert LDMF Screens NOTE The images below are for representation of the menu items only. The actual display including the Controls and Indicators shown in the images below may not be present. Figure 2 Main panelboard screens—examples Panelboard Main Screen...
SUBFEED LABEL IX CF = X.X IX THD = XX.X IY CF = X.X IY THD = XX.X IZ CF = X.X IZ THD = XX.X NEXT SUB FD BACK HELP | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
NEXT GROUP BRANCH SELECT BACK BACK HELP HELP Branch Alarms PANEL BOARD LABEL BRANCH LABEL NO ALARMS PRESENT or OVER CURR ALRM OVER CURR WARN UNDER CURR WARN BACK HELP | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
1% for 2 - 100A 5% for 100-120A Minimum Current 200mA ENVIRONMENTAL Humidity 0-95% Temperature (Non-Operating) -68°F to 158°F (-20°C to 70°C) Temperature (Operating) 32°F to 104°F (0°C to 40°C) | Liebert® LDMF™ Distribution Monitoring User Manual | Vertiv ™...
Verify the PC is connected to the LDMF Setup port and the communication cable (F-F null modem DB9) is fully seated (see 5.2.1 - LDMF Setup Port Connection). • Verify the Liebert LDMF unit has power (green LEDs on the BCB will be flashing). How can I make a backup copy of the configuration file? •...