Page 1
NetSure™ Monitor Unit User Manual (UM1M832DNA), Revision C Specification Number: 1M832DNA Model Number: M832DNA Software Version 1.0...
Page 2
This document may contain confidential and/or proprietary information of Vertiv Group Corp., and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Vertiv Group Corp.
Information Screens (accessed from the Main Menu) ..........40 Alarm Menu ................................41 Settings Menu ................................ 42 Bay Current Menu .............................. 46 Input Feeds Current and Voltage Menu ..................47 Distribution Panels Menu ........................... 48 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 4
Accessing the Monitor Unit via TL1..............152 Accessing the TL1 Port ..........................152 Port Connection ................................152 TL1 Port Connection Keep-Alive Feature ..................152 TL1 User Session .............................. 152 Establishing a Session ............................152 TL1 Autonomous Messages ..........................152 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 5
TL1 Autonomous Messages Supported (in alphabetical order) ....... 167 List of Error Codes for TL1 Commands Supported (in alphabetical order) ....................................171 Replacement Procedures ................... 172 Monitor Unit Replacement ........................172 Specifications ......................174 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
(ISO) SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Each panel consists of up to 28 distribution devices. A bay has multiple feeds, which are connections to incoming DC power. One or more panels are connected to each feed. This picture shows these components: Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Alarms can be assigned one of the following alarm severity levels. • Critical Alarm: The fault endangers the systems continued function. • Major Alarm: The fault reduces the systems functionality. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Data History log contains historical values for key system data points. • System Log: Records 3000 items in run log. The Web Interface displays the latest 500 items. System log contains internal history to assist with field troubleshooting by Vertiv personnel. NOTE! For all logs, once maximum number of log entries is reached, new entries overwrite the oldest entries.
Web page. Refer to “Consumption Map Tab” on page 65. Refer also to “Consumption Map Settings Tab Programmable Parameter Descriptions” on page 69. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The system has one or more active Alarm Observation alarms. Alarm (Yellow) conditions are programmable. Major or The system has one or more active Critical Alarm Major or Critical alarms. Alarm (Red) conditions are programmable. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Description: There are four (4) menu navigation keys and a local display located on the monitor unit’s front panel. Refer to Table 4 for the function of the menu navigation keys. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Press the UP and DOWN keys to move up and down the list of parameters. Press ENT to select the parameter. Press the UP and DOWN keys to change the parameter. Press ENT to make the change. Press ESC to cancel the change. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The default settings for these parameters are shown below. • Link-Local Address: fe80:209:f5ff:fe09:1002/64 • IPv6 Address: 20fa:fffd:fffc:fffb:fffa:fff9:fff8:fff7 • IPv6 Prefix: 0 • IPv6 Gateway: 20fa:1:fffe:ffff:fffe:fffd:ffff:fffe Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 15
Some systems may have an IB4 board with a second Ethernet port. This port supports Dynamic Host Configuration Protocol (DHCP) function. Refer to your system’s documentation for location of the IB4 board (if furnished). Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 16
IPv4 IP Address: Subnet Mask: Default Gateway: Example: IP Address: 192.168.1.2 Subnet Mask: 255.255.255.0 Default Gateway: 192.168.1.1 IPv6 IPv6 Address: IPv6 Prefix: Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 17
IB4 board (if furnished). An Ethernet port is located on the top panel of the monitor unit. This port supports Dynamic Host Configuration Protocol (DHCP) function. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 18
Internet Explorer is used in this procedure, other browsers are similar. Launch “Internet Explorer”. Internet Options Tools Select from the menu. The “Internet Options” window opens. In the “Internet Connections Options” window, select the tab. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 19
Internet Explorer is used in this procedure, other browsers are similar. Launch “Internet Explorer”. Internet Options Tools Select from the menu. The “Internet Options” window opens. In the “Internet General Options” window, select the tab. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 20
The following window opens. In the Every time I visit the webpage window, choose “ ” and click OK. Security In the “Internet Options” window, select the tab. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 21
In the window, type or copy the monitor unit URL in the “ ” box. Websites Close Click . The monitor unit URL is listed in the : box. Click Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Users (see “Users Tab” on page 89). To program the Alarm Reporting SMTP section, in the Web Interface, go to Advanced Settings Menu / Alarm Report Tab / SMTP Section / enter at a minimum Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
“Advanced Distribution Panel Settings Web Page” on page 63. Changing the Date and Time Local Menu Navigation: Main Menu / Settings Icon / Sys Settings / Date. Main Menu / Settings Icon / Sys Settings / Time. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 24
IPv6 Communications Parameters (if monitor unit not set as DHCPv6)” on page 14. Local Menu Navigation: Main Menu / Settings Icon / Comm Settings / enter parameters. Web Menu Navigation: Advance Settings Menu / Ethernet Tab / enter parameters. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 25
Advance Settings Menu / TL1 AID Group Tab. Set the TL1 access identifiers and sub-access identifiers as described under “TL1 AID Group Tab” on page 118. Enabling/Disabling and Configuring Pre-Defined TL1 Signals Local Menu Navigation: None. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 26
Programming the Audible Alarm Feature Local Menu Navigation: Main Menu / Settings Icon / Sys Settings / Audible Alarm. Web Menu Navigation: None. Blocking Alarms Local Menu Navigation: None. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 27
Home Page / Distribution Bay Tab / navigate the various interactive elements screens and select Clear Data in the settings screens. Clearing Logs Local Menu Navigation: None. Web Menu Navigation: Advance Settings Menu / Clear Data Tab / select log to clear. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 28
A file named "SettingParam.tar" is automatically created/appended by the monitor unit whenever a User (or the factory at the time of shipment) makes changes to parameter settings via the Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 29
• One step to reload the saved monitor unit configuration package. • One step to reload the saved "SettingParam.tar" file. Refer to the following procedures. Reloading the Configuration Package Local Menu Navigation: None. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 30
Web Menu Navigation (To Download an Application ("All") Package): Advance Settings Menu / SW Maintenance Tab. See “Upload/Download Procedure” on page 99 to download an Application (“All”) Package into the monitor unit. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 31
At the Main Screen, press ENT and ESC at the same time to reset the monitor unit. Web Menu Navigation: Advance Settings Menu / SW Maintenance Tab / Reboot Controller button. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Specifically, refer to the current issue of the following Bellcore publications for further information on the NMA system and TL1 command language. TR-NWT-000831 TR-NWT-000833 TR-NWT-000835 TR-NWT-000199 TA-NWT-000199 TA-NWT-000200 TA-NWT-001360 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The interface is available from the monitor unit when the monitor unit uses a fixed IP address or a DHCP address. The interface only supports one request/query at a time. Using the Machine-to-Machine HTTP Interface Option Refer to the following. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 34
The <title> fields are the Full English Name of the samples in the table. There is one title for each signal which is sampled. The titles are enclosed in double quotes. Response Data Each row is one line. Each line is separated by a CR/LF. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 35
The data value in a row is the data at or before the one minute interval for that row. Example: System Voltage is sampled every 5 minutes. The samples are: 54.2V at 12:10.10 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
FA/CB alarm on panel A, C, E, or G. open. See why fuse or circuit breaker is FA CB Alarm Panels BDFH FA/CB alarm on panel B, D, F, or H. open. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 38
OFF position. or closing. Check for overload or short circuit. The SM-DUH2 has lost SMDUH2 Communicate Failure Check communications cables. communications with the controller. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The Main Menu is shown in Figure 3. This is the first screen displayed when the local display is activated by pressing any key on the monitor unit’s top panel. Figure 3: Main Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Information Screens (accessed from the Main Menu) Information screens can be accessed from the Main Menu as shown in Figure 4. Figure 4: Information Screens Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Alarm Menu The Alarm Menu can be accessed from the Main Menu as shown in Figure 5. Figure 5: Alarm Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Settings Menu The Settings Menu can be accessed from the Main Menu as shown in Figure 6. Figure 6: Settings Menu - Menu Selection Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 43
Clear Datas: Clear (Clear) Press ENT to make the change. Press ESC to cancel the change. The parameter values shown in ( ) are the adjustment range or acceptable values. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 44
Clear Datas: Clear (Clear) Press ENT to make the change. Press ESC to cancel the change. The parameter values shown in ( ) are the adjustment range or acceptable values. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 45
(No / Yes) Update App: The parameter values shown in ( ) are the (No / Yes) adjustment range or acceptable values. Figure 11: Settings Menu - Comm Settings Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Bay Current Menu The Bay Current Menu can be accessed from the Main Menu as shown in Figure 12. Figure 12: Bay Current Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Input Feeds Current and Voltage Menu The Input Feeds Current and Voltage Menu can be accessed from the Main Menu as shown in Figure 13. Figure 13: Input Feeds Current and Voltage Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Distribution Panels Menu The Distribution Panels Menu can be accessed from the Main Menu as shown in Figure 14. Figure 14: Distribution Panels Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
High Curr Lmt2: Enter the distribution device’s high current 2 alarm setpoint. Enter the percentage value of the "capacity" for alarm. Breaker Poles: Enter the number of poles the distribution device has. Clear Datas: Clears the data stored for the distribution device. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
• Restore Default: Restores the monitor unit’s default settings. • Update App: Updates the monitor unit’s application. Comm Settings Sub-Menu • Protocol: Select "EEM", "TL1",or "Modbus" as the protocol. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 51
• IPV6 Prefix: Sets the monitor unit's IPv6 prefix. • IPV6 Gateway: Sets the monitor unit's IPv6 gateway address. Enter the address in the format nnnn:nnnn:nnnn:nnnn:nnnn:nnnn:nnnn:nnnn, nnnn must follow IPv6 address rules. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The homepage window is divided into six areas: System Status Information Area System Specifications Information Area Monitor Unit Specifications Information Area Alarms Area System Status Area Menu Navigation Area Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
System specifications are displayed here. Monitor Unit Specifications Information Area Monitor unit specifications are displayed here. Figure 16: System Status Information, System Specifications Information, and Monitor Unit Specifications Information Areas Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Critical tab to display alarms set as Critical alarms. NOTE! Observation alarms are color-coded yellow, major alarms are color-coded orange, and critical alarms are color-coded red. Figure 18: Critical Alarms Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Web page. For example, clicking on the Feed # 1 element opens the Web Page shown in Figure 21. This topic is further explained in the next sections. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 56
• High Current Limit 2: Enter the bay’s high current 2 alarm setpoint. Enter the percentage value of the "capacity" for alarm. • Number of Panels: Enter the number of panels installed in the bay. • Clear Data: Clears the data stored for the bay. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 57
24/week/month are not recorded until the period has passed (meaning the total for 24 hours isn't recorded until 24 hours have passed, etc.). Figure 21: Feed Web Page Clicking here opens the following Web page. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 58
• Feed Full Name: Name displayed in the Web Interface menus. • Feed Abbr Name: Name displayed in the local display menus. • Over Volt1: Enter the feed’s over voltage 1 alarm setpoint. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 59
• Shunt Voltage: Enter the feed’s shunt voltage rating. • Shunt Current: Enter the feed’s shunt current rating. • Clear Accumulated Data: Clears the data stored for this feed. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 60
The Standard Distribution Panel Web Page allows you to view standard distribution panel data and set standard distribution panel parameters. Figure 23: Standard Distribution Panel Web Page Clicking here opens the following Web page. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 61
• Num of Distribution Elements: Enter the number of distribution devices that are installed in the distribution panel. • Clear All Data: Clears the data stored for the panel. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 62
The Advanced Distribution Panel Web Page allows you to view advanced distribution panel data and set advanced distribution panel parameters. Figure 25: Advanced Distribution Panel Web Page Clicking here opens the following Web page. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 63
• Num of Distribution Elements: Enter the number of distribution devices that are installed in the distribution panel. • Clear All Data: Clears the data stored for the panel. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 64
"capacity" for alarm. • Breaker Poles: Enter the number of poles the distribution device has. • Clear All Data: Clears the data stored for the distribution device. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
• Red Icon: Customer load current is greater than Alarm Level 2. • Grey Icon: Customer load current is 0. • White Icon: Customer load has not been configured. Figure 28: Consumption Map Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Bay Data Tab The Bay Data tab displays general status information as shown in the following illustration. Figure 29: Bay Data Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Changing Programmable Parameters in the Settings Menu To change a programmable parameter, select or enter a new value for the parameter then click on “Set” to change the value. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 68
Manual Date and Time Menu • Signal Settings: Outgoing Alarms Blocked: Normal: Alarms are processed normally. Blocked: Forces the alarm relays in the "off" state and blocks alarms from changing the relay state. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 69
For the Firefox Browser: On the tool bar, right side, click on the icon with the 3 horizontal bars. Verify that the zoom level is set to 100%. Figure 33: Settings Menu - Consumption Map Settings Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 70
Once a load distribution device has been designated, it will become greyed out and cannot be dragged again. You can add up to twenty (20) load distribution devices to a customer load icon. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 71
Figure 36: Dragging Load Distribution Device Icons Click the "Show Designation" button to see the designation selected. Figure 37: Show Designation Before Designate Button is Clicked Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 72
Figure 38: Show Designation After Designate Button is Clicked Click the "Designate" button to set the designation. Figure 39: Load Distribution Devices Designated to Customer Load Icon Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 73
• Alarm Level 2: If the customer load(s) exceeds the percent of the total device current rating entered for Alarm Level 2, the icon representing the customer load turns red, which indicates an major alarm. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 74
• Get time automatically from the following servers. When selected, the monitor unit will get the time from the selected time server. The monitor unit will also adjust the time per the "Local Zone" setting. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Select Device and Time Select the "Device" to query from the drop-down list box. Select the "from" and "to" time. Figure 42: Alarm History Log Device and Time Selection Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 76
Query Alarm History Log Click “Query” to query for alarms within selected time slot. The Web page displays the last 500 entries. Figure 43: Alarm History Log Query Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 77
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 44: Alarm History Log Upload Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 78
Event log contains a history of key parameter changes made by Users via the LCD or web pages. Select Time Select the "from" and "to" time. Figure 45: Event Log Time Selection Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 79
Query Event Log Click “Query” to query the Event Log. The Web page displays the last 500 entries. Figure 46: Event Log Query Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 80
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 47: Event Log Upload Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 81
Data History log contains historical values for key system data points. Select Device and Time Select the "Device" to query from the drop-down list box. Select the "from" and "to" time. Figure 48: Data History Log Device and Time Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 82
Query Data History Log Click “Query” to query for Date History within selected time slot. The Web page displays the last 500 entries. Figure 49: Data History Log Query Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 83
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 50: Data History Log Upload Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 84
System Log Tab System log contains internal history to assist with field troubleshooting by Vertiv personnel. Select Time Select the "from" and "to" time. Figure 51: System Log Time Selection Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 85
Query System Log Click “Query” to query the System Log. The Web page displays the last 500 entries. Figure 52: System Log Query Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 86
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 53.: System Log Upload Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The System Inventory Menu allows you to view product information of the intelligent devices (i.e. rectifiers, converters, SMDUs, IB, etc.) connected to the monitor unit. Figure 54: System Inventory Menu Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
IPv6: IPv6 Address, IPv6 Prefix, and IPv6 Gateway. After modifying the network parameters, click "Save" to validate the change made to the parameters. NOTE! After changing the IP Address, you will need to login again with the new IP address. Figure 55: Ethernet Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 89
Re-enter the password for this User in the "Confirm" field. Click the "Add" button to add the User. NOTE! To reset the form (i.e. to start over) and erase all information entered, click on the “Reset” button. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 90
Users. The User has full access to all menus; including Level D (Administrator) admin, 640275 update the OS application and modify, add, and delete Users. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 91
To reset the form (i.e. to start over) and erase all information entered, click on the “Reset” button. Deleting an Entry Select the Entry to be deleted from those listed at the top of the screen. Click the "Delete" button to delete this Entry. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 92
To reset the form (i.e. to start over) and erase all information entered, click on the “Reset” button. Figure 57: SNMP - NMSV2 Configuration IPV6 checkbox appears once you start typing an NMS IP. Check the IPV6 box when entering an IPV6 address. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 93
Monitor unit must be reset after configuration of initial SNMP v3 User (Advanced Settings Menu / SW Maintenance Tab / Restore Factory Defaults / Reboot Monitor Unit). Figure 58: SNMP - NMSV3 Configuration Check the IPV6 box when entering an IPV6 trap address. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 94
Figure 59: Language Tab Figure 60: Selecting the Local Language for the Local Display and Web Interface Menus Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 95
SW Maintenance Tab Allows you to perform software maintenance procedures. Figure 61: SW Maintenance Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 96
The monitor unit will automatically reboot. All settings WILL BE restored to the defaults of the stored configuration package. NOTE! After rebooting, you must exit your browser and re-login to see any changes made. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 97
Figure 62: Restore Factory Defaults Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 98
"SettingParam.tar" files saved. The new name can use alpha and numeric characters preceding the original “SettingParam.tar” name (the end of the new file name must always be “SettingParam.tar”; for example, an acceptable filename would be “seville4SettingParam.tar”). Figure 63: Retrieve SettingParam.tar Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 99
Maintenance Tab, click on the “Stop Controller” button. Figure 64: Upload/Download - Stop Monitor Unit The following window opens. Figure 65: Upload/Download --Monitor Unit Stopped Click "OK". The following window opens. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 100
A Language Package is a package of files containing all the default names of the parameters in two languages. Typically these would be in English and Chinese. The language package cannot be changed by the User. Consult Vertiv if a different language package is required. NOTE! A file named “SettingParam.tar”...
Page 101
• Allows you to define the alarm level for each alarm. (See also Table 1 on page 9.) • Allows you to map alarms to the alarm relays. Figure 67: Alarms Tab Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 102
The following window opens. Select the New Alarm Level and/or New Relay Number and click on “Set”. “None” means there is no related relay number. Figure 68: Setting Alarm Level / Relay Number Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 103
To change the relay signal full name (name displayed in the Web Interface menus), click on the “Modify” button for that relay. The following window opens. Figure 70: Changing Relay Signal Full Name Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 104
• Server Port: Server port. Obtain from your IT department. • Email From: The monitor unit or Site email address. Will be displayed in the email from field of the received email. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 105
SMTP Password: SMTP password. Obtain from your IT department. • Alarm Report Level: If you only want to use the Forgot Password Feature, set the Alarm Report Level to None. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 106
Monitor Protocol Tab To make the new protocol valid, click the “Valid after Restart" button and then “OK” in the confirm to change window. Figure 73: Valid after Restart Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 107
The monitor unit restarts. Figure 74: Restart Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 108
• Second Report IP: Enter parameters per site requirements. • Security Connection IP 1: Enter parameters per site requirements. • Security Connection IP 2: Enter parameters per site requirements. • Safety Level: Select per site requirements. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 109
Alarm Bit 0: Normal 1 : Alarm Alarm Level 00: None 01: Observe 10: Major 11:Critical Current in Amps Voltage in Volts Power in kW Energy in kWh Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 110
Relay4Status Mode 0 Read 0xFFFF Number of Critical Alarms Mode 0 Read 0xFFFF Number of Major Alarms Mode 0 Read 0xFFFF Number of Observation Alarms Mode 0 Read 0xFFFF Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 112
Bit 8: Current Hi2 Alarm 0: Normal 1: Alarm Bit 10-9: Current Hi2 Alarm Alarm Level 00: None 01: observer 10: Major 11: Critical Bit 11: reserve Bit 12-15: reserve Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 114
Bit 8: SM-DUH2 Comm Read 0xFFFF Loss 0: Normal 1: Alarm Bit 10-9: SM-DUH2 Comm Loss Alarm Level 00: None 01: observer 10: Major 11: Critical Bit 11: reserved Bit 12-15: reserved Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 115
Write/Read Remark Value Value Panel A 3016 same as above Position 2 Panel A 3032 same as above Position 3 … Panel H 8120 same as above Position 40 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 116
This is a unique name which identifies the monitor unit in an NMA system. This data parameter is used to identify the destination of command messages and the source of response and autonomous messages in an NMA system. Set per site requirements. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 117
Select the data log to be cleared from those listed in the drop-down list box. Click on the “Clear” button to clear the corresponding data. Figure 78: Clear Data Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 118
Thirty-two (32) monitor unit access identifiers can be programmed into the monitor unit. The access identifier is used to uniquely identify a system entity (such as rectifiers contained in the power plant). Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 119
• ENV, refers to environment entities or entities that are external to the NMA system (ex. air conditioners, fans, etc.) Click the submit button. Repeat these steps for the remaining Access Identifiers (AID). Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 120
The field has one of two values - ‘active’ or ‘inactive’. Setting the signal to ‘active’ will enable the signal for monitoring and processing of the associated alarm signals for TL1 commands and reports. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 121
Refer to TA-NWT-001360 Table 6-1. Click the Submit button. Repeat these steps for other signals to be added to the AID group and to assign signals to other AID groups. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
With SSL, you can browse/set the Webpage with https. Data is encrypted in the transmission. You can also browse/set the MIB library with SNMP v3. Data is also encrypted in the transmission. SNMP V3 IE Browser MIB Browser Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The User permitted to access the agent. The get/set data security level (NoAuthNoPriv, AuthNoPriv, or AuthPriv). The private DES password used to encrypt the data. The authorization MD5 password used to encrypt the digital signature. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
MIB Installation Installation The Monitor unit’s MIB is named "Netsure-Distribution.mib". Contact your Vertiv representative for the location on the Web to download the MIB file. Use the MIB loading function of the NMS to load the MIB database. Refer to the User Manual provided with the NMS for the detailed loading method.
Page 125
SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION " 1.3.6.1.4.1.6302.3.1 which is the base OID for the information in this MIB ." ::= { system 2 } sysUpTime OBJECT-TYPE Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 126
(2^(4-1) + 2^(7-1)). Note that in the context of the Internet suite of protocols, values should be calculated accordingly: layer functionality physical (e.g., repeaters) datalink/subnetwork (e.g., bridges) internet (e.g., IP gateways) Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 127
Indicates 'activated' (1) or 'deactivated' (2) alarm events." SYNTAX INTEGER { activated(1), deactivated(2) } EnableState ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION " Indicates 'enabled' (0) or 'disabled' (1)" SYNTAX INTEGER { Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 128
Indicates 'one' (0) or 'two' (1) or 'three' (2) or 'four' (3) or 'five' (4) or 'six' (5) or 'seven' (6) or 'eigth' (7)" SYNTAX INTEGER { one(0), two(1), three(2), four(3), five(4), six(5), seven(6), eight(7) } panelPositionString ::= TEXTUAL-CONVENTION STATUS current Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 129
::= { ident 2 } identControllerFirmwareVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION " The firmware (software) version of the controller." ::= { ident 3 } identName OBJECT-TYPE SYNTAX DisplayString Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 130
MAX-ACCESS read-only STATUS current DESCRIPTION " Maximum output power over the past 24 hours in Watts " ::= { bay 4 } bayPeakPowerLastWeek OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 131
::= { bay 11 } bayRelay2Status OBJECT-TYPE SYNTAX RelayState MAX-ACCESS read-only STATUS current DESCRIPTION " On/Off status of relay 2. 0=off 1=on" ::= { bay 12 } bayRelay3Status OBJECT-TYPE Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 132
SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION " Threshold for high-high current alarm in 0.001 % " ::= { bay 19 } bayNumberOfPanelPositions OBJECT-TYPE SYNTAX PanelPositionNum MAX-ACCESS read-write STATUS current Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 133
A through H (assigned by the controller),a(0) or b(1) or c(2) or d(3) or e(4) or f(5) or g(6) or h(7)" ::= { panelEntry 2 } panelName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 134
::= { panelEntry 9 } -- FA/CB alarm Fuse/circuit-breaker alarm condition -- SM-DUH2 comm loss Communication lost with the SM-DUH2 for this panel ------------------------------------------------------------ -- 6302.4.1.2.3 Feed values { sys 3 } ------------------------------------------------------------ Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 135
"Automatically generated index object." ::= { feedEntry 1 } feedID OBJECT-TYPE SYNTAX Integer32(1..8) MAX-ACCESS read-only STATUS current DESCRIPTION " 1 through 8 (assigned by the controller)" ::= { feedEntry 2 } Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 136
STATUS current DESCRIPTION " Maximum output power over the past 30 days in Watts" ::= { feedEntry 9 } feedTotalEnergyLast24hrs OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION " Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 137
::= { feedEntry 16 } feedOverVoltage2 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION " Threshold for over-voltage alarm 2 in mV" ::= { feedEntry 17 } feedUnderVoltage1 OBJECT-TYPE SYNTAX Integer32 Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 138
-- Under Voltage #1 Under-voltage alarm condition -- Under Voltage #2 Under-voltage alarm condition -- High Current #1 Over-current alarm condition -- Very High Current #2 Over-current alarm condition ------------------------------------------------------------ Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 139
::= { deviceEntry 1 } devicePanel OBJECT-TYPE SYNTAX panelPositionString MAX-ACCESS read-only STATUS current DESCRIPTION " The panel containing this device (A=1, B=2, etc.)." ::= { deviceEntry 2 } deviceID OBJECT-TYPE Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 140
::= { deviceEntry 9 } devicePeakPowerLastMonth OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION " Maximum output power over the past 30 days in Watts" ::= { deviceEntry 10 } Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 141
::= { deviceEntry 16 } deviceCurrentBreakerSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION " Rating of the fuse/CB in mA" ::= { deviceEntry 17 } deviceHighCurrentLimit1 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 143
::= { loadEntry 6 } loadPeakPowerLastMonth OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION " Maximum output power over the past 30 days in Watts" ::= { loadEntry 7 } loadTotalEnergyLast24hrs OBJECT-TYPE Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 144
SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION " Threshold for high current alarm in 0.001 %" ::= { loadEntry 14 } loadHighCurrentLimit2 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 145
MAX-ACCESS read-only STATUS current DESCRIPTION " The unique sequence number of this alarm trap." ::= { activeAlarmEntry 1 } alarmTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION " Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 146
An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmIndex - The unique sequence number of this alarm trap. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 147
* alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm." ::= { powerEvents 3 } ------------------------------------------------------------ -- End of MIB definitions ------------------------------------------------------------ Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 148
Total/cumulative output energy since last reset, stored as 0.001kWh bayRelay1Status On/Off status of relay 1. 0=off 1=on bayRelay2Status On/Off status of relay 2. 0=off 1=on bayRelay3Status On/Off status of relay 3. 0=off 1=on Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 149
Threshold for the low voltage alarm 2 in mV feedCurrentBreakerSize Rating of the fuse/CB in Amps feedCurrent1Limit Threshold for high current alarm in 0.001 % feedCurrent2Limit Threshold for very high current alarm in 0.001 % Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 150
Threshold for very high current alarm in 0.001 % alarmIndex The unique sequence number of this alarm trap. Date and time when event occured (local time), including timezone if alarmTime supported by controller. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 151
(local time), including timezone if supported by alarmCeaseTrap controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
• Once a valid TL1 port User session is established, valid request messages will be accepted. TL1 Autonomous Messages • Autonomous TL1 messages are outputted through the TL1 port whenever one is pending and there is a valid port connection. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Requests a system RTRV-HDR <null> not used header message. REPT-ALM- Report of alarms as varies EQPT they occur and clear. CANCEL- User timeout <null> not used SESSION message. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 154
<atag> is the autonomously generated ID (like a sequence number) <rspblk> is the detailed information about the alarm; see details below. Verb <response parameter blocks> REPT-ALM-EQPT Alarm details. CANCEL-SESSION <null> Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
The monitor unit responds with this message: Lorain 15-09-25 08:17:55 40 COMPLD "SYSTEM:M830B::SWVER=1.00,CURSWVER=1.1.41T04,:IS-NR," < The monitor unit type is M830B. The configuration is version 1.00. The software version is 1.1.41T04. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 156
Here is an example of the monitor unit response when an invalid command (RTRV-ALM-EQPTX::ALL:57::CR;) is sent: Lorain 15-09-25 08:18:15 57 DENY ICNV /* Command not valid */ < Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Instructs the system to send the current monitor unit RETRIEVE-EQUIPMENT software version and the monitor unit software configuration RTRV-EQPT part number and revision. RETRIEVE-HEADER Requests that the system reply with a "normal" response RTRV-HDR indicating COMPLD. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
^^^<source identifier>^<date>^<time> cr lf M^^<ctag>^COMPLD cr lf ^^^/* This is a private computer system. cr lf Unauthorized access may result in criminal prosecution */ cr lf; Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 159
No response is returned if a valid User session has not been established. Otherwise the response is in the following format. cr lf lf ^^^<source identifier>^<date>^<time> cr lf M^^<ctag>^COMPLD cr lf Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 160
This is the effect on service caused by the alarm condition. Valid values for this parameter are as follows: service-affecting condition nonservice-affecting condition <null> request retrieval of alarm conditions for both of the above codes Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 161
This is the notification code associated with a single alarm condition given in this block. <condtype> This is the condition type of the alarm condition being given in this block. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 162
The following parameters will either not be implemented or do not apply to this application. A <null> value is returned for these parameters. <aiddet> - supplementary equipment identification <obsdbhvr> - observed behavior that resulted in reported trouble Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 163
<exptdbhvr> - expected behavior that was deviated from <dgntype> - diagnostic routine used to isolate trouble <tblistl> - provides isolation information Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 164
Version of software that is actually installed. This is an ASCII string from one to thirty-two characters. The value of this parameter is the monitor unit’s software version (e.g., “1.30”). If no software version is available, the value is <null>. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 165
<sst> This is the secondary state of the equipment. This parameter is not available in this application. A value of <null> is always outputted for this parameter. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 166
Input Format: RTRV-HDR:[<tid>]:<aid>:<ctag>; <aid> The <aid> in this command must be <null> since it does not apply. Normal Response Format: cr lf lf ^^^<source identifier>^<date>^<time> cr lf M^^<ctag>^COMPLD cr lf Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Message Format: cr lf lf ^^^<sid>^<YY-MM-DD>^<HH:MM:SS> cr lf A^^<atag>^CANC cr lf <uid> cr lf ; <uid> This is the User whose session is terminated as a result of the timeout. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 168
CL code which is used when reporting an alarm has cleared. <condtype> This is the condition type of the alarm. It indicates the type of failure that has occurred/cleared. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 169
This parameter is a text message which provides a detailed description of the alarm, event, or condition. It is an ASCII string enclosed within a pair of escaped quotes (\”). It may also be used to Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 170
- observed behavior that resulted in reported trouble <exptdbhvr> - expected behavior that was deviated from <dgntype> - diagnostic routine used to isolate trouble <tblistl> - provides isolation information Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Wait for the monitor unit to finish booting and verify that the complete system operates normally. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 173
Figure 81: Monitor Unit Configuration Label Location Configuration File Part Number Label Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
• Electrical: IEC 60950-1, EN 60950-1, UL 60950-1 • EMC: EN 300 386, 2001 Class B; FCC Part 15, Class B • Environmental: CE; NEBS Level 3 • GR-3108 Class 2 Compliant Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...
Page 175
This page is intentionally blank. Vertiv | NetSure Monitor Unit User Manual (UM1M832DNA) | Rev. C...