How to Configure
By selecting this menu, assign a name to the new network.
In this example "Danfoss" has been chosen.
Illustration 3.2 Assigning a Network Name
After clicking [OK], the network "Danfoss" should show up
under Networks and by selecting the Network, the main
configuration page is shown.
Illustration 3.3 Main Configuration Page
MCA 122 Modbus TCP
Menu
Model Family
Model Utilities
IP address configu-
ration
Ethernet Configu-
ration
Table 3.4 Menu Settings
In the IP Configuration tab, press the [Configured] key, and the IP
address and fill out [Subnetwork mask]. In this example the address
192.168.1.20 is used as the address for the master.
The step assigns the protocol to the scanner, which is done
by selecting the scanner and selecting the "Function" menu
and enables the Ethernet by selecting "ETH TCP IP" This brings
up the Net Link menu, where "Danfoss" has to be selected. At
this time, the "Danfoss" Protocol is assigned to the Scanner
and the last step is to configure the scanner to read and write
holding registers of the FC 302.
®
MG90P202 - VLT
is a protected Danfoss trademark
Menu point
Setting
Model Family
NOE 0100, NOE 110
IO Scanning
YES
Global Data
NO
Address Server
NO
Configured/From a
Configured
server
IP address
192.168.001.020
Subnetwork mask
255.255.255.0
Gateway address
0.0.0.0
Ethernet Configu-
Ethernet II
ration
3
3
13