ICM Controls I3 1010HR Installation, Operation & Application Manual page 27

Thermostat with humidity control auto changeover dual power
Table of Contents

Advertisement

Symptom
Heat or Cool not coming on
Setpoints do not display all of the time
displays
displays
Remote Sensor
OVERRIDE displays
Condensation forming on windows
Thermostat says that the humidifier is
operating but humidity has not risen
Dehumidifier is always running
The room temperature is met, but the air
conditioner is still operating
Offline !
Troubleshooting (continued)
Verify wiring is correct, gently pull on each wire to verify there is a good
connection at terminal block.
Press
,
Check for low battery condition or faulty outdoor/remote temperature sensor.
Check remote sensors temperature at
Program schedule is in temporary override, it will return to schedule at the next
transition time.
Decrease humidification setting
Check humidifier pad and replace if necessary
Check the relay configuration (Section 22, Page 17).
Dehumidification is set to COOL -2. The thermostat will continue to let the
cooling system operate until the cooling temperature is 3°F below the setpoint or
when the dehumidification setpoint is met.
If the thermostat or APP shows offline ( !) for more than a few minutes, unplug
the thermostat from the wall plate, wait one minute, then plug thermostat back
into wall plate.
Remedy
MENU
,
six times,
VIEW
MENU
,
,
,
.
VIEW
27