Commissioning, Decommissioning; Commissioning; Decommissioning; Trouble Shooting - Mastervolt Mass Sine Ultra 24/4000 User And Installation Manual

Sine wave inverter
Table of Contents

Advertisement

7 COMMISSIONING, DECOMMISSIONING

7.1

Commissioning

CAUTION!
Check
the
polarity
commissioning: plus connected to plus (red
cables), minus connected to minus (black
cables).
The DIP-switches must be adjusted prior to
commissioning; see chapter 6.
Follow the steps described below to switch on the Mass Sine
Ultra.
1
Tighten all strain reliefs;
2
Check all wiring and connections;
3
Close the front cover plate of the connection
compartment;
4
Place the DC-fuse(s) of the DC-distribution to connect
the batteries to the Mass Sine Ultra.
WARNING
When placing this fuse, a spark can occur,
caused by the capacitors used in the Mass Sine
Ultra. This is particularly dangerous in places with
insufficient ventilation, due to the gassing of the
batteries an explosion can occur and avoid
having flammable materials close by.
Now the Mass Sine Ultra is ready for operation.
7.2

Decommissioning

If it is necessary to put the Mass Sine Ultra out of operation,
follow the instructions in order of succession as described
below:
1
Move the Main-switch of the Mass Sine Ultra to "Off";
2
Remove DC-distribution fuses and/or disconnect the
batteries;
3
Open the connection compartment of the Mass Sine
Ultra;
4
Check with a suitable voltage meter whether the input
and the output of the Mass Sine Ultra are voltage free;
5
Disconnect all the wiring.
Now the Mass Sine Ultra can be demounted in a safe way.
of
all
wiring
before
EN / Mass Sine Ultra
7.3

Trouble shooting

If a failure occurs, the origin of the failure is displayed by
means of the LED's at the front of the Mass Sine, see figure
7-3.
Figure 7-3: Error LED's
The table at section 7.3.1 shows the meaning of the error
indications and their solutions, together with other directions.
If you cannot solve a problem using this table, contact your
local Mastervolt Service Centre. See www.mastervolt.com.
Make sure you have the following information present if you
have to contact your local Mastervolt Service Centre to solve
a problem:
Article and serial number (see section 1.7).
Software version (see summary page in MasterAdjust or
the Configuration page in MasterView control panel).
23

Hide quick links:

Advertisement

Table of Contents
loading