This consists the total length of the cable, not the length between two boilers. The length differs with the diameter of the cable.
2)

Appendix E - NTC sensor curve selection (Rev 3 .0 .0 .0)

The NTC curve of each sensor can be changed between LabVision PC software.
The NTC curve can be selected from a list of pre-defined curves.
Setting
NTC Curve
0
NTC 10K @ 25°C B3435
1
NTC 10K @ 25°C B3977
2
NTC 10K @ 25°C B3760
10
NTC 10K @ 20°C B3457
20
NTC 12K @ 25°C B3740
30
NTC 12K @ 25°C B3970
(*) Duplex safety sensors cannot be adjusted freely.

Appendix F - 5 Error table (Rev . 4 .0 .905 .17114)

In the next tables a description of all different errors is given.
Errors can be divided in three groups:
• Non-volatile locking errors (can only be reset by the reset button).
• Blocking errors (will disappear when error is gone)
• Warnings (will disappear when the warning is gone, also isn't stored in the e2prom)
When the control is in error the pump will be running. This is to prevent the freezing of the Central Heating circuit when the boiler is in error during the
winter period. For some non-volatile lockouts the pump will not be running, also see the error tables in this chapter for more details.
F .1
Boiler history and time stamps
Boiler History
Via the Boiler History screen in the LabVision PC software the following history data is shown:
• Successful ignitions
• Failed Ignitions
• Flame Failures
• Hours in Operation
• CH Burner Minutes
• DHW Burner Minutes
SSB
L× W × H
212×152×47mm (8,35"×5.98"×1,85")
530 gram
Service reminder | 55
6720892984 (2019/02) US