70 | Service reminder
Access
Holding
register
R
W
...
599
REMARKS
a
NV Non-Volatile means that the parameter is stored in the non-volatile memory (eeprom, flash, etc). These parameters will retain their value
after a reset/power cycle. However the parameters have a limited amount of allowed write cycles (10.000 times, average of 2 times per day),
which means these parameters cannot be used for dynamic control!
V Volatile, means that the parameter is stored in the volatile memory (RAM). These parameters will lose their value after a reset/power
cycle (value will be reset to the last know setting from non-volatile memory). These parameters can be written unlimited and can be used for
dynamic control. The Error Log items can be read in blocks of 8 holding registers from error log index 0 to 47 (total 48 error log items).
K .3 .5
Service Reminder (1500 – 1550)
The Service Reminder status and settings can be read/written using the following holding registers.
To check if the Service Reminder is active, the Hours_Till_Service (1501) holding register should be read.
When the Hours_Till_Service value is 0 the service reminder is active.
Acces
Holding register
R
1500
X
1501
X
...
1530
X
1531
X
1532
X
1533
X
NOTE: A Overdue counter value of 0xFFFF means that the counter is not available/empty.
6720892984 (2019/02) US
Description
Reserved...
Reserved...
Description
W
Service Reminder Counters
Hours since last service (Burn hours or operation hours,
depends on the Service_Hour_Counter setting).
Hours till service is required (Burn hours or operation
hours, depends on the Service_Hour_Counter
setting).
Reserved...
Service Settings
X
Reset Service Reminder.
Service Hour Counter setting. The counted hours (1500
X
+ 1501) are burn / operation hours.
X
Service Interval.
Service Shutdown Period (after service reminder is
X
active).
Automatic
Remarks
Conversion
Automatic
Conversion
0...65534 hours.
0...Service_Interval
0...1 (1=Reset).
0=Burn hours,
1=Operation hours.
0...25500 hours (Steps of 100 hours).
0...25500 hours (Steps of 100 hours).
Range
Range
SSB