2.11

Minimum clearance

With a horizontal flue outlet, make sure the electronic components
inside the boiler at the top remain accessible when placing an elbow
directly on the flue outlet adapter.
▶ After fitting the flue bend, check whether the upper panel of the
appliance is easy to remove (§ 7.2, p. 18).
▶ There must be a clearance of at least 100 mm directly above the flue
bend at the boiler.
2
3
1
S
5,2 %
(52 mm/1 m)
Fig. 4
Side view [mm]
[1]
Horizontal flue outlet
[2]
Collar
[3]
Vertical flue outlet
A
Clearance from top of the boiler - center of hole
B
Clearance from top of the boiler - upper side of hole
C
Depth of the boiler - 587,5 mm
K
Diameter of hole
S
Wall thickness
Wall thickness S K [mm] for Ø flue outlet [mm]
Ø 110/160
15 - 24 cm
190
24 - 33 cm
195
33 - 42 cm
200
42 - 50 cm
205
Table 2 Diameter of core drilled hole K
Condens 7000 WP – 6721842519 (2022/03)
136
C
0010040879-001
Ø 110
140
145
150
155
Flue exhaust
Ø 110 mm
Connection adapter with
elbow, horizontal flue outlet.
Ø 110/160 mm
Ø 110 mm
Connection adapter, vertical
flue outlet
Ø 110/160 mm
Table 3 Clearance A and B depending on flue outlet
Calculate the minimum clearance above the boiler.
▶ Add dimension B from Table 3 to the height of the top of the boiler.
▶ With a horizontal flue outlet:
– Add 52 mm to dimension B for every meter of horizontal flue
outlet.
– In this case also take the diameter of the collar into consideration.
▶ With a vertical flue outlet:
– Maintain a clearance of at least 100 mm above the boiler to allow
the electronic components to be accessed and worked on.
Minimum space required for the boiler.
▶ Provide an unobstructed space of at least 100 cm for the boiler to
allow maintenance and other work to be carried out.
Minimum space required next to the boiler.
▶ Maintain an area of at least 5 mm on the either side of the boiler.
≥ 5*
Fig. 5
Front view [mm]
2.12

Flue gas temperature sensor

The boiler is manufactured with a flue outlet sensor as standard ( Fig.
1, p. 6).
The flue gas temperature sensor protects the boiler and flue system from
high flue gas temperatures by reducing the boiler load (downward
modulation).
Product Information
A [mm] B [mm]
165
A + 0.5*K
179
A + 0.5*K
-
0
-
0
≥ 5*
260
300
520
0010033512-001