58 | Service reminder
Error no .
Error
106
REFHI_TOO_HIGH
107
REFHI_TOO_LOW
108
REFLO_TOO_HIGH
109
REFLO_TOO_LOW
110
REFHI2_TOO_HIGH
111
REFHI2_TOO_LOW
112
REFLO2_TOO_HIGH
113
REFLO2_TOO_LOW
114
FALSE_FLAME
115
LOW_WATER_PRESSURE_ERROR
116
LOW_WATER_PRESSURE_SENSOR
117
BLOCKED_DRAIN
118
WD_COMM_ERROR
119
RETURN_OPEN
120
SUPPLY_OPEN
121
SUPPLY2_OPEN
122
DHW_OPEN
123
FLUE_OPEN
124
FLUE2_OPEN
125
OUTDOOR_OPEN
126
RETURN_SHORTED
127
SUPPLY_SHORTED
128
SUPPLY2_SHORTED
129
DHW_SHORTED
130
FLUE_SHORTED
131
FLUE2_SHORTED
132
OUTDOOR_SHORTED
133
RESET_BUTTON_ERROR
134
PHASE_NEUTRAL_RESERVED_ERROR
135
T_EXCHANGE_BLOCK_ERROR
136
T_CHIMNEY_OPEN
137
T_EXCHANGE1_OPEN
138
T_EXCHANGE2_OPEN
139
T_SELECTION1_OPEN
140
T_SELECTION2_OPEN
141
T_SELECTION3_OPEN
142
T_OPTIONAL1_OPEN
143
T_OPTIONAL2_OPEN
144
T_AMBIENT_OPEN
145
T_CHIMNEY_CLOSED
146
T_EXCHANGE1_CLOSED
147
T_EXCHANGE2_CLOSED
148
T_SELECTION1_CLOSED
149
T_SELECTION2_CLOSED
150
T_SELECTION3_CLOSED
151
T_OPTIONAL1_CLOSED
152
T_OPTIONAL2_CLOSED
153
T_AMBIENT_CLOSED
154
WD_CONFIG_ERROR
155
FLUE_PRESSURE_ERROR
156
AIR_DAMPER_ERROR
157
T_SECONDARY_SUPPLY_OPEN
158
T_SECONDARY_RETURN_OPEN
159
T_SECONDARY_SUPPLY_CLOSED
160
T_SECONDARY_RETURN_CLOSED
161
FILL_WARNING
6720892984 (2019/02) US
Description
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Flame is detected in a state in which no flame is allowed to be seen
Low water pressure error
Low water pressure
Block drain switch is active
Watchdog communication error
Return sensor open
Supply sensor open
Supply 2 sensor open
DHW sensor open
Flue sensor open
Flue 2 sensor open
Outdoor sensor open
Return sensor shorted
Supply sensor shorted
Supply 2 sensor shorted
DHW sensor shorted
Flue sensor shorted
Flue 2 sensor shorted
Outdoor sensor shorted
Too many resets in a short time period
The live and neutral of the main voltage power supply input are reversed
Exchange temperature exceeded 90°C.
Chimney sensor open
Exchange 1 sensor open
Exchange 2 sensor open
Selection 1 sensor open
Selection 2 sensor open
Selection 3 sensor open
Optional 1 sensor open
Optional 2 sensor open
Ambient sensor open
Chimney sensor shorted
Exchange 1 sensor shorted
Exchange 2 sensor shorted
Selection 1 sensor shorted
Selection 2 sensor shorted
Selection 3 sensor shorted
Optional 1 sensor shorted
Optional 2 sensor shorted
Ambient 1 sensor shorted
Watchdog fan configuration setting error
Flue pressure switch is closed
Air Damper feedback is not received when the relative output is closed
Secondary circuit supply sensor open
Secondary circuit return sensor open
Secondary circuit supply sensor shorted
Secondary circuit return sensor shorted
Pressure is too low, demand has stopped, but no error needed to be stored at
this time
SSB