54 | Service reminder
Menu item
Sub item / Parameter
(163) Hyst Up Stop Boiler
(164) Hyst Down Quick Start
(165) Hyst Up Quick Stop
(166) Hyst Up Stop All
(167) Number of boilers
(168) Power Mode
(169) Max. Setp. Offset Down
(170) Max Setp Offset Up
(171) Start Mod Delay Fact
(172) Next Boiler Start Rate
(173) Next Boiler Stop Rate
(174) Boiler Rotation Interval
(175) First Boiler to Start
(176) PID P
(177) PID I
(178) PID Slew Rate Up
(179) PID Slew Rate Dn
(180) PwrMode2 Min Power
(181) PwrMode2 Hysteresis
(182) Post-Pump period

Appendix D - Control System Technical Specifications

The 900 series burner controls have the following specifications:
Power Supply
Ambient Temperature
Humidity
Fuses
Flame establishing period
Safety time
Ignition attempts
Pre purge time
Pre ignition time
Flame failure response time
Flame-detection
Flame-current
Protection
Standards
Cable length AL-BUS ²
)
6720892984 (2019/02) US
Range
0...40 (0...72)
0...40 (0...72)
0...40 (0...72)
0...60 (0...108)
1..8
0) Disabled
2) Max burners
3) Balanced burners
0...40 (0...72)
0...40 (0...72)
0..60
10..100
10..100
0..30
1..8
0..1275
0..1275
0..25,5
0..25,5
0..100
0..100
0..255
230V/120VAC
(-15%, +10%) 40Hz to 70Hz
Functional
-15 to +70°C (5°F to +158°F)
(Peak temperatures, not continuous)
Storage
-25°C to +75°C (-13°F to 167°F)
900MN: 93% RV at 25°C (77°F)
Mains input
1 x 5AT, 250V
2 seconds
5 seconds
3
≥ 2..60 seconds (not safety critical)
Default: 6s
2 seconds (not safety critical)
< 1,0 second
Ionization measurement via separate ionization rod
Minimum
1.0 μA
Start-detection
1,5 μA
Maximum
14.0 μA (only max. on measurement inside control)
IP00; Protection against electrical shock must be guaranteed by the appliance
According to EN60529
manufacturer.
Europe: CE EN298:2003
AGW
23
20
18
17
15
Default Value
Units
2 (4)
°C (°F)
10 (18)
°C (°F)
4 (7)
°C (°F)
8 (14)
°C (°F)
1
2
20 (36)
°C (°F)
20 (36)
°C (°F)
20
Min.
80
%
25
%
5
Days
-
25
1000
1
1
20
%
40
%
30
Sec.
A(mm2)
0,25
0,5
0,7
1
1,5
User Level
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
3: Factory
3: Factory
3: Factory
3: Factory
2: Installer
2: Installer
2: Installer
Cable length
(m)
100 (328.1ft)
200 (656.2ft)
300 (984.3ft)
400 (1312.3ft)
600 (1968.5ft)
SSB