The following table shows the sensor availability for all CH and DHW
control modes. Sensors that are not mentioned in the table are optionally
available for other functions.
0
T_Supply
M
T_Supply_2
-
T_Return
-
T_DHW
-
T_Outdoor
D
0-10 Volt
-
Water Flow DHW
-
RT switch
M
0
1
T_Supply
-
M
T_Supply_2
-
-
T_Return
-
-
T_DHW
D
M
T_Outdoor
-
-
0-10 Volt
-
-
Water Flow DHW
-
-
RT switch
-
-
Legend:
M Mandatory
- Optional
D Disabled
The T_Flue and T_Flue_2 sensors do not store the sensor open error.
This is to protect the system going to a blocking state in very cold
conditions.
SSB
CH mode
1
2
3
4
M
M
M
M
-
-
-
-
-
-
-
-
-
-
-
-
M
M
-
-
-
-
M
-
-
-
-
M
M
M
M
DHW mode
2
3
5
6
7
M
-
-
M
M
-
-
-
M
-
-
-
-
D
-
D
M
M
M
D
-
-
-
D
D
-
-
-
-
-
-
-
M
-
M
M
-
-
-
-
5 .3 .6
Pump start every 24 hours (Rev 3 .0 .0 .0)
To protect the pump from getting stuck at a certain position it is forced to
run for 10 seconds every 24 hours. This is done only for the CH pump at
the start-up of the board.
5 .3 .7
Frost protection (Rev 3 .0 .0 .0)
The frost protection function protects the system from freezing.
The T_Supply , T_Supply_2 and T_Return sensors are checked for
generating a frost protection demand.
• When any of the sensors drop below FP_start_pump the pump is
switched on for CH.
• When any of the sensors drop below FP_start_burn the burner is
started.
• When all of the sensors measure above FP_stop the frost protection
demand is ended.
When the demand for frost protection is ended the pumps will post-
8
circulate for CH_Post_Pump_Period . Relevant variables
M
-
Relevant variables
M
M
Specific Parameters Level
-
FP_start_pump
-
[°C/°F]
FP_start_burn
M
[°C/°F]
E2_FP_stop
-
[°C/°F]
5 . 3 . 7 . 1
Frost protection
In cascade systems frost protection is active on 3 levels.
[4] Boiler cascade controller
[5] Burner cascade controller
[6] Burner
The start temperatures should be defined so that the cascade handlers
are the first to trigger the protection. When there is a CH/DHW call for
heat, the frost protection will be overridden and the control will start for
CH/DHW. When frost protection stops the pumps go to post purge.
The display may show "Frost protection" when it is activated.
Specific Parameters Level
Cascade frost
protection
[°C/°F]
Temperature for frost
protection
Frost protection for boiler cascade
The 'frost protection' function for a boiler cascade is related to the system
sensor temperature.
When the system sensor temperature is below:
Cascade frost protection
The cascade CH/system pump and the general pump of the managing
burner in the managing boiler start running.
Main control | 35
(Default) Value
Settable
°C
°F
°C
3: Factory 10
50
-10..117 14..243
3: Factory 5
41
-10..117 14..243
3: Factory 15
59
-10..117 14..243
(Default) Value
Settable
°C
°F
°C
2: Installer 15
59
10..30
6720892984 (2019/02) US
°F
°F
50...86