Connecting To 10Base5 Network - Mitsubishi MELSEC-Q series User Manual

Fl-net(opcn-2) interface module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

5.2 Connecting to 10BASE5 network

(1) Connecting an AUI cable
*1: Never connect the AUI cable when the power to the station with a module
mounted is on.
(2) Wiring to the external power supply terminal (DC power supply for
transceiver (*1))
The following explains how to connect a cable to the external power supply
terminal (DC power supply for transceiver).
1) Strip the cable jacket back 13mm. (*2)
The applicable cable size is 0.13mm
2) Loosen the terminal screw and insert the cable into the terminal.
3) Tighten the terminal screw within the torque range shown in Section 3.1.
*1: Use a transceiver that is equipped with a function generally called as SQE
TEST or heartbeat (a signal that is used for checking normal transceiver
operation after transmission).
*2: If the wire strip length is too long, the conductive part is exposed and it may
increase the risk of electric shock or short circuit between the adjacent
terminals. If the wire strip length is too short, it may result in poor contact.
Retainer
A
B
AUI cable
Power supply for transceiver
13mm
(0.51 in.)
<Operating procedure>
(Step 1) Slide the retainer in
(Step 2) Insert the AUI
(Step 3) Slide the retainer in
(Step 4) Check that the AUI
2
(AWG26) to 2.5mm
7
direction B
connector all the way.
(*1)
direction A
cable is locked.
2
(AWG14).