Honeywell DPS CANopen User's & Technical Manual page 15

Digital pressure sensor
Table of Contents

Advertisement

Digital Pressure Sensor with CANopen
'Table 17. Transmission Types Supported by the Digi-
tal Pressure Sensor with CANopen
Transmission
Description
(hex)
Acyclic, synchronous transmission. The Digi-
tal Pressure Sensor with CANopen
DPS, will transmit a PDO message after
0
occurrence of the SYNC, but only if an event
(change in the pressure data) occurred
before the SYNC.
Cyclic, synchronous transmission. The
Digital Pressure Sensor with CANopen
1-F0
Model DPS, will transmit the PDO message
on reception of the nth SYNC message,
where n is 1 to 240.
Asynchronous transmission. The Digital
Pressure Sensor with CANopen
DPS, will transmit the PDO message at the
FE
time interval defined by the event time (by
default it transmits pressure data every 100
millisec). The PDO is transmitted without any
relation to the SYNC object.
Asynchronous transmission. The Digital
Pressure Sensor with CANopen
DPS, will transmit the PDO message at the
FF
time interval defined by the event time (by
default it transmits pressure data every 100
millisec).The PDO is transmitted without any
relation to the SYNC object.
Table 19. Command to Change Physical Units from psi to Bar
ID(hex) DLC
Data(Hex)
Byte0
Byte1 Byte2 Byte3
67F
8
40
31
5FF
8
60
31
67F
8
40
30
5FF
8
60
30
67F
8
22
31
5FF
8
60
31
67F
8
40
31
5FF
8
60
31
67F
8
40
30
5FF
8
60
30
, Model DPS
®
, Model
®
,
®
, Model
®
, Model
®
Byte4 Byte5
61
01
00
00
61
01
00
00
61
01
00
00
61
01
50
C3
61
01
00
00
61
01
00
00
61
01
00
00
61
01
00
00
61
01
00
00
61
01
78
0D
, Model DPS
®
7.2 Changing the Output Units
The default unit of the process value is psi. The physical units
of the process value can be read or modified by using the ob-
ject 6131. When the units are changed using the object 6131,
the units of all the objects associated with process value is
changed internally by the Digital Pressure Sensor with CANo-
pen
, Model DPS. Table 18 contains the list of the objects that
®
are associated with process value. The Model DPS supports
only 1 PDO.
Table 18. List of Objects Affected by Unit Change
Object
Description
6148
AI span start
6149
AI span end
6124
AI input offset
6130
AI input process value REAL32
2006
Span
Description
Byte6 Byte7
Read the current
00
00
unit
AB
00
Current unit is psi
00
00
Read process value
00
00
50 psi
Change the unit to
4E
00
bar
00
00
Return ok
Read the current
00
00
unit
4E
00
Current unit is bar
00
00
Read process value
00
00
3.448 bar
Sensing and Productivity Solutions
50085804, Rev. B