Warnings and Alarms
LCP message
Status
!1(1)
0 RPM
None
0.00KW
SO Reset required!
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SO in Self-test
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SF pending
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SafeOpt. initialised
!Safe Stop [W68]
MG34W302
Operating Instructions
Description
In the following cases, the
safety option requests a
restart and failure acknowl-
edgement-signal:
1. The safety option is in
safety function pending-
state (Remark: Occurs only
if reset behaviour is set/
configured to 'manual')
2. After a power cycle with a
safety function
3. In PUST (power up self
test), if an external failure
occurred before power
cycle
4. When an external failure
occurred
5. When customisation was
aborted or completed
6. At the reception of a
general reset (required
after blank initial state or
in the customisation
state.)
The safety option indicates
that it is PUST State (Power
Up Self Test).
1. Ensure that no safe
function is active after a
power cycle.
A safety function is pending
at the start-up, if the
frequency converter was
powered down while a safety
function was active.
It is also pending, when the
frequency converter was
powered down while the
safety option has detected a
failure during an active safety
function.
The safety option requests a
'Restart and Failure
Acknowledge signal', which is
always required after a PUST
and when a safety function
gets released and is
configured to be confirmed
that the motor is able to run.
Danfoss A/S © Rev. 2014-02-11 All rights reserved.
LCP message
Status
!1(1)
0 RPM
None
0.00KW
SO General Reset
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SO Suspend-SpeedMon
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SO Warning PUST
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SO Warning DI1
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SO Warning DI2
!Safe Stop [W68]
Status
!1(1)
0 RPM
None
0.00KW
SO Suspend-SpeedMon
!Safe Stop [W68]
Table 8.3 LCP Messages
Description
Occurs only if general reset is
performed from MCT 10. It is
an indication to the user. The
safety option is set to blank
initial state and safe
parameters are set to default.
Zero speed timer contains
the remaining time until the
fail prec thresh timer elapsed
after the monitoring time
expires. The safety option
signals Warning.
PUST warning has occurred.
Warning cause: Expiry of
PUST timer. Memory test
required, perform power
cycle.
DI1 offline warning has
occurred.
Warning cause: Expiry of
offline timer for DI1.
DI2 offline warning has
occurred.
Warning cause: Expiry of
offline timer for DI2.
Speed monitoring suspension
warning has occurred.
Warning cause: Suspension of
speed monitoring for certain
duration.
69
8
8