Danfoss VLT MCB 150 Operating Instructions Manual page 44

Hide thumbs Also See for VLT MCB 150:
Table of Contents

Advertisement

General Parameter Set-up
Group
Group Name
42-2*
Safe Input
6
6
42-3*
General
42
Operating Instructions
Parameter
Value range/
available choices
42-20 Safe Function [0] STO
[1] SS1-a
[2] SS1-b
[3] SLS-a
[4] SLS-b
[5] disable
42-21 Type
[0] NCNC
[1] Antivalent
[2] NC
42-22 Discrepancy
0 - 5000 ms
Time
42-23 Stable Signal
0 - 5000 ms
Time
42-24 Restart
[0] Manual
Behaviour
[1] Automatic
42-30 External
[0] STO
Failure Reaction
[1] SS1-a
[2] SS1-b
42-31 Reset Source
[0] Drive Reset
[1] Drive Safe Reset
[2] Safe Option
DI2_A
42-33 Parameter Set
Visible String,
Name
length: 8
Danfoss A/S © Rev. 2014-02-11 All rights reserved.
Default
Description
[0] STO
This can be one of
the safety functions
or disabled. Remark:
Both Safe Inputs can
NOT be disabled at
the same time!
[0] NCNC
NCNC, antivalent
(NC/NO) or 1NC.
10 ms
An adjustable filter
time prevents faults
caused by temporary
discrepancy.
10 ms
An adjustable signal
filter in the safety
option suppresses
temporary signal
changes using test
pulse pattern.
[0] Manual
In case of an
activated safety
function, the safety
option can either
restart automatically
or wait for a RESET
signal from the user.
[0] STO
Safety function that is
executed in case of
an external failure.
[0] Drive Reset
Source for the RESET
of the safety option.
Can either be
executed on the
option input DI2, via
fieldbus or digital
input on the
frequency converter
or via the LCP. By
selecting Drive Safe
Reset, only the safety
option is reset.
SafeSet1
Name of the safe
parameter Set (must
be 8 characters to
avoid a bad customi-
sation data error).
Conversion
Data type
index
-
u_int8
-
u_int8
-3
u_int16
-3
u_int16
-
u_int8
-
u_int8
-
u_int8
MG34W302