Danfoss VLT MCB 150 Operating Instructions Manual page 54

Hide thumbs Also See for VLT MCB 150:
Table of Contents

Advertisement

Service and Repair
manufacturer hereby proves to have tested the
effectiveness of the safety functions used. The commis-
sioning test must be performed on the basis of the risk
analysis. All applicable standards and regulations must be
adhered to.
The machine is properly wired
Check the effectiveness of all safety components
used in the application
All safety equipment such as protective door
monitoring devices, light barriers or emergency
stop switches is connected and ready for
operation
All motor parameters and command parameters
must be set correctly on the frequency converter
A commissioning test of the safety option must be
7
7
performed in the following situations
After the configuration of each machine
After changing the safety option parameters
After making changes to the machine (as per
applicable standards and regulations)
Check the effectiveness of all safety functions used.
1.
Document each individual step of the test.
2.
Note the checksum of the safety option
parameters in the records.
3.
Do NOT release the system unless it has
successfully passed all individual steps of the test.
4.
Restart the frequency converter and check that
the motor runs normally.
52
Operating Instructions
Danfoss A/S © Rev. 2014-02-11 All rights reserved.
MG34W302

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt mcb 151

Table of Contents