Warnings and Alarms

8.2 Warnings and Alarms
NOTICE
The errors are listed numerically.
Error
No.
Description
Internal failure
Reason
1
Diagnostic in
progress
67
Int Fail
Check that data for
tolerance error
feedback (ppr., type of
exceeded:
feedback and gear
Reaction STO
ratio) are entered
correctly
Direction of feedback
is wrong
Due to use of
feedback filter the
dynamic of the system
does not match with
dynamic of feedback
filter (42-15 Feedback
Filter). System is
ramping too fast.
Feedback signals are
not received at all
No proper shielding of
feedback cables
68
Int fail Speed
The value of Delta V is
limit SS1a
too small. For closed
Ramp: Reaction
loop system it must
STO
often be larger than
the recommended
value.
Due to use of
feedback filter the
dynamic of the system
does not match with
dynamic of feedback
filter (42-15 Feedback
Filter).
Load change takes
place during ramping.
69
Int fail Speed
See 68
limit SS1b
Ramp: Reaction
STO
MG34W302
Operating Instructions
Led Indications
Action
Make a re-customi-
sation with correct
data if needed
Set 42-12 Encoder
Direction to the
opposite value
Decrease ramping
time on frequency
converter
Try to run the
system at e.g. 60
RPM. If error nr. 99
now occurs, this is
the reason.
Improve shielding
of feedback cables
and motor cables.
Status of LED 1 and LED2 depends on safety
function state assigned to DI1 and DI2
If running in closed
loop, try to adjust
PID setting and if
needed increase
SS1 ramping time.
Try to increase
42-15 Feedback
Filter, but this
might cause error
nr. 67 to occur.
Otherwise increase
42-45 Delta V.
See 68
Danfoss A/S © Rev. 2014-02-11 All rights reserved.
LED1
LED 2
LED4
Green
constant
Green
constant
Red constant
8
8
Red constant
Red constant