Maintenance; Environmental; Gas Sampling And Filling - ABB SafeLink Installation And Operating Instructions Manual

Sf6 insulated ring main unit
Table of Contents

Advertisement

SafeLink
abb
SF
Insulated Ring Main Unit
6
Installation and Operating Instructions

3 Maintenance

3.1 Environmental

The SafeLink switching enclosure is a gas-tight welded stainless steel compartment able
to withstand a harsh environment. However, it is important that the base of the SafeLink
installation be kept free of vegetation or other material to prevent corrosion of the stand
and/or enclosure.
3.2 Maintenance
All components within the SF
insulated tank are maintenance free for the life
6
expectancy of the unit. The tank is made of stainless steel.
Scratches or other damage to panels must be repaired.
Mechanical parts located outside the sealed tank are surface treated or made of
corrosion resistant materials. These parts are lubricated during manufacture for the
unit's life expectancy.
Units installed in extreme conditions are likely to require inspection depending on the
nature of the environment.
Where an outdoor enclosure is used, this should be checked periodically for scratches or
corrosion and the base of the stand must be kept clear of vegetation and well ventilated.

3.3 Gas Sampling and Filling

The gas density gauge on the front of the SafeLink shows the density of SF
gas in the
6
unit. All units are tested to ensure that any leakage rate is so low as to give a thirty-year
service life. During switching, the arc formed will cause the gas to dissociate. Once the
arc is extinguished the SF
reforms. A molecular sieve is fitted inside the switching
6
enclosure to absorb any remaining ion products.
When samples are required these are taken through the Dilo fitting of the gas density
gauge on the front of the unit in the fuse compartment. Therefore, the fused switch must
be switched to the earth position and the selector placed in the blocked position. The
sample must be taken with the sampling kit available from ABB. This will ensure that
any gas escaping during the sampling process is minimised.
Gas is added through the same connection used to take samples. The ABB filling
adaptor allows the pressure inside the switch to be monitored during filling. Full details
are included with the filling adaptor.
SLMIO ver 2.12
ABB Ltd, Switchgear Division, Auckland, New Zealand
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents