Programming
P-17: Reset Memorized Defaults
The default programming parameters can be reset as follows:
➤ Select "rSt".
✓ This restores the programmable parameters to the default values.
The default parameters listed in the "Programmable Parameters Table" on page 17
may be altered by the installing dealer or end user. Once new defaults are entered
and memorized the factory defaults will be overwritten. The original factory program
parameters as listed in the table may be restored manually.
P-18, P-19: Reserved for Future Option
P-20: Filter Threshold
This feature is to remind you to change the air filter on a unit. The units are x10 hours.
By default it is off, which is designated with a "00", but it can be set between 100 and
2500 hours. After the unit has reached its threshold time, it will display a "FIL" remind
1 s every 10 s.
P-21: Current Filter Time
This feature is used to display the amount of time the current filter has been on the
unit. The units are x10 hours.
➤ In order to reset this parameter, simply press the Up or Down Button.
P-22: Voltage Calibration
This feature displays the voltage reading as seen by the display. Calibrating this
parameter will provide a more accurate voltage when calculating low voltage for P-7.
It will display a live reading of the voltage.
➤ Manipulate the reading by pressing the Up or Down Button.