How to Use the Node Terminal Block
Example of connection mode 1)
System information (24 words) and Area to send to computer (512 words) are sent over the Data Link.
Leading address S
Leading address S+24
Leading address S+535
Node: 01, Link start word: S
Node
01
02
The Loop Control Unit uses the 1-Block Send Terminal to Computer or 4-Block Send Terminal to Computer to
send Control blocks such as PID blocks that are to be monitored on CX-Process Monitor to the Area to send
to computer.
It also uses the DO to Computer or AO to Computer block to send contacts (including parameters) or analog
signals (including parameters) to this Area to send to computer.
By the user settings of the Controller Link Data Link, a total of 536 words comprising system information (24
words) and Area to send to computer (512 words) are sent to the computer.
In this way, the following Send to Computer blocks in the Loop Control Unit are sent (allocated) to the 512
words of the Area to send to computer in Data Memory area for node terminals in order of block address (501
onwards through to 532) one function block at a time at a fixed rate of 16 words per function block. (512 words
is calculated by (max.) 32 function blocks x 16 words.)
Note
A fixed number of words (512) is used even if 32 function blocks are not used.
1-Block Send Terminal to Computer (Block Model 403)
4-Block Send Terminal to Computer (Block Model 404)
DO to Computer (Block Model 401)
AO to Computer (Block Model 402)
The Control block or contact/analog signals can be monitored on CX-Process Monitor based on that data.
Using Controller Link to connect to CX-Process Monitor
Loop Control Unit
Controller Link unit
PC#1
Data Memory (D) for Node Terminal
Â
For LCU number
8 words
0
System
information
For LCU number
8 words
1
#1
For LCU number
8 words
Â
2
512 words
Area to send to computer
(16 words x 32 blocks)
#1
Â
Send/
Leading
Number
Receive
word of
of words
self node
Send
S
536
words
Á
Á
Receive
OFF
Controller Link
Support Board
Controller Link
Leading address P
24 words
Node: 02, Link start word: 20
Offset
Node
Send/
Receive
Á
01
Receive
Á
02
Send
OFF
Note: Status information of the Controller Link Data Link is
allocated to words 0 to 19.
CX-Process
Monitor
PC #32
Â
For LCU number
0
System
information
For LCU number
1
#1
For LCU number
2
Area to send to computer
#1
Leading
Number
Offset
word of
of words
self node
20
536
0 word
words
Á
Á
Appendix 2
225