Nortec SETC Warnings and Faults
The self-diagnostic system built into the SETC is continually monitoring the operation of the
humidifier.
Warnings
When problem symptoms are detected, the Nortec SETC will attempt to take self-corrective
actions to try to correct the problem. A warning is displayed on the screen for information
purposes and the humidifier continues to operate.
If the condition which generated the warning is eliminated the warning is cleared from the
display.
Faults
If the humidifier is not able to self correct a problem symptom it will if necessary respond by
shutting itself down.
When this occurs the humidifier illuminates the red "Fault" LED, shuts off the signal to the
CV valve actuator, and activates the "Error" relay of the remote relay board.
Clearing a Fault
Check the fault message that the humidifier is displaying and take any necessary actions to
correct the cause(s) as outlined in Table 13, Troubleshooting Warnings and Faults.
Power cycle the humidifier with the On/Off switch waiting 3 seconds between turning it off
and on.
Code
Display
Message
CLF
Clock Fault
DCF
Drain Ck Fault
Table 13: Troubleshooting Warnings and Faults
LED
System Detected
Controller
Red
system clock
failure.
The drain pump
is activated but
Red
water level has
not decreased
Cause
1 Software has detected
a hardware problem
with main control
board
1 Drain blocked
2 Pump not working
Corrective Action(s)
1 Restart humidifier, if
error occurs within 1
minute replace main
control board. If error
does not occur then
primary power
fluctuation may be the
cause.
1 Check water flow at air
gap when drain
activated. Flow should
be > 5 gal (20 l) / min.
2a Check wiring to pump.
2b Activate pump with
diagnostic output test
and verify pump runs
and drains water.
Troubleshooting | 76