Steam Lines and Condensate Returns
MAIN RULES FOR ATMOSPHERIC STEAM LINES
Slope the steam lines.
Trap condensate (Use full size 'T' for Traps).
Steam lines must not have any restrictions which could cause back pressure.
Insulate with 1.0 in. (2.5 cm) pipe insulation.
Follow recommended materials, size and length see tables.
Use Appropriate Slope
10 Degrees
0.5 in.
(12 mm)
Steam Line
Material
Lb/hr (kg/hr)
0-100 (0-45)
Copper Tube
101-250 (46-113)
251-650 (114-295)
0-100 (0-45)
*Stainless Steel
101-250 (46-113)
Tube
251-650 (114-295)
Condair Hose
31-100 (14-45)**
Note:
* Use only stainless steel tube for reverse osmosis and deionized water applications.
** Use 2 x 4 in. steam lines for steam capacities higher than 750 lb/hr (307 kg/hr)
*** Use one steam hose per 100 lb/hr (45 kg/hr) of output.
Steam Hose Odour: Condair hose may generate a slight odour during initial use.
This odour is temporary and will disappear after a short period of time.
17 | Installation
1 ft (30 cm)
2 Degrees
St eam Dire ction
1ft (30 cm)
Figure 12: Main Steam Line Requirements
Table 5: Recommended Steam Line Material
Steam Line Length
ft
0-90
0-180
0-260
0-90
0-180
0-260
<15
Insulate Pipe
2 in.
(5 cm)
1 in. (2.5 cm) pipe
insulation
m
Steam Line Description
0-27
1 1/2 in. MED-L Tubing (1.625 in. OD)
0-54
3 in. MED-L Tubing (3.125 in. OD)
0-79
**4 in. MED-L Tubing (4.125 in. OD)
0-27
1.75 inch Tube x 0.065 inch thick wall
0-54
3 inch Tube x 0.065 inch thick wall
**4 inch Tube x 0.065 inch thick wall
0-79
<4.5
***Part Number 1328820 (1 3/4")