User Defined Settings

The selections in User Defined Settings allow you to configure most user configurable features
available with the Nortec SETC. Press Set while highlighting User Defined Settings in the Main
Menu.
User Defined Settings
Drain Cool
: On
Drain Cool
: Off
BD Rate
: 25%
FTBD
: Off
FTBD Time
: Off
FTBD Hours
: 100
Idle Mode
: Idle Drain
Idle Time
: 72 hr
Fill Corr
: 100%
Drain Corr
: 100%
Float Ck
: 23:30
Date
: 06/27/09
: 13:22
Time
Unit
: lb/hr
Language
: English
Contrast
: 10
Leak Ck
: Off
Set
Menu
BD Rate
: 25%
FTBD
: Off
FTBD Time
: Off
FTBD Hours
: 100f
51 | Operation
Drain Cool
On
Off
On
On
Smart
Menu
Set
Blowdown Rate
25%
Menu
Set
Full Tank Blowdown
Off
On
On
Menu
Set
FTBD Time
Hour
23
Hour
23
Menu
Set
FTBD Hours
100
100
100
Menu
Set
Drain Cool
Selects whether drain water cooling
will be performed by adding fill water
to drain water. Off = fill valve not
activated during drain. On = fill valve
activated whenever drain pump is
on, Smart = fill valve only activated
with drain pump when tank is hot.
(Default = Smart)
Blowdown Rate
Sets the amount of water as a
will be drained to control mineral
concentration in the tank. (Default –
25%)
Full Tank Blowdown
Sets whether the tank will be
periodically flushed to help flush
minerals and scale. Blowdown
frequency is controlled by the FTBD
Hours parameter below. (Default =
On)
FTBD Time
Sets the time of day when a full tank
interrupting humidifier operation
during critical times. (Default =
23:30)
FTBD Hours
Sets the number of hours between
full tank blow downs. Hours are
accumulated on a weighted basis (1
hour at 50% demand = 0.5 hrs).
(Default = 100 hr)