Performance Characteristics - Honeywell VG.010A Product Handbook

Universal gas valves, safety solenoid valves
Table of Contents

Advertisement

PERFORMANCE CHARACTERISTICS

Maximum allowable leakage
Model
Test pressure 1
(mbar)
(mbar)
VG .010
VG .015
VG .020
VG .025
VG .032
VG .040
VG .050
VG .065
VG .080
Opening time
Valves are manually opened
Closing time
Less than 1 second
Duty cycle
Coil suitable for permanent
energization
EN2R--9012 9412R0--NE
Test pressure 2
6
6
6
6
6
6
6
6
6
Operational voltage range
The safety solenoid valve will funtion
satisfactory between 85% and 110% of
the rated voltage.
Rated voltage:
24 V, 50/60 Hz
110 V, 50/60 Hz
220 V, 50/60 Hz
240 V, 50/60 Hz
Design life
5.000 cycles
(mbar)
(mbar)
750
750
750
750
750
750
750
525
525
Maximum allowable leakage rate (cm
Internal
40
40
40
60
60
60
60
60
60
3
/
)
h
External
40
40
40
60
60
60
60
60
60
6