VGF Flanged Globe Valves
VGF21
VGF31
APPLICATION
VGF Flanged Globe Valves are used for 2-position or
modulating control of steam, hot water, or chilled water in
closed loop HVAC systems. They can be operated by a
large variety of electric and pneumatic actuators. Three-
way valves are available in mixing or diverting flow
patterns.
FEATURES
• ANSI Class 125 and Class 250 flanged cast iron
bodies.
• Face-to-face flange dimensions per ANSI/ISA S75.03
standard.
• Sizes from 2-1/2 to 6 inches (DN65 to DN150).
• Metal-to-metal seating for long life span.
• Differential pressure of 175 psi, ANSI Class IV
leakage on pressure-balanced models.
• Steam inlet pressure up to 100 psig (689 kPa).
• Self-adjusting packing.
• Equal percentage and linear flow characteristics to
ensure precise control in a variety of applications.
Related Literature
— 62-0213 VGF Installation Instructions
— 63-1301 VGF Specification Data
— 63-9271 Field Devices Catalog (for compatible
actuators)

SPECIFICATIONS

VGF22
Models: See Tables 2 and 3.
Dimensions: See Fig. 3 and 4.
Action:
Mixing valves: Stem up to close port A-AB.
All others: Stem down to close port A-AB.
Controlled Media:
Water up to 50% glycol solution.
Saturated steam (2-way models) up to 100 psig.
Not suitable for open loop systems such as condenser
VGF32
Valve Body Temperature-Pressure Ratings:
Water: ANSI Class 125 and 250. See Table 1.
Steam: 337°F (170°C); 100 psig (689 kPa).
Flow Capacity: See Table 8.
Stroke and Mounting:
2-1/2 and 3 inch (DN65 and DN80): 3/4 in. (20mm)
4 to 6 inch (DN100 to DN150): 1-1/2 in. (38mm) stroke,
Maximum Temperature Differential
(alternating hot/cold water): 108°F (60°C).
Flow Characteristic:
VGF2__E_: Equal percentage.
VGF2__L_: Linear.
VGF3_EM_ Mixing Valve: Equal percentage port A-AB, Lin-
VGF3_LD_ Diverting Valve: Linear.
Rangeability: 50:1.
Close-Off Pressure (maximum):
VGF21_P pressure-balanced: 175 psi (1207 kPa).
All others: Proportional to actuator force. See Tables 4, 5.
Leakage Rate (maximum):
VGF21_P pressure-balanced: 0.01% of Cv (ANSI Class IV).
VGF2__S: 0.05% of Cv (ANSI Class III).
Three-way:
water or potable water.
stroke, 1-3/8 in. bonnet, 1/4-28 UNF stem thread and
button.
1-7/8 in. bonnet, 7/16-20 UNF stem thread, and but-
ton.
ear port B-AB.
and 6.
VGF31EM and VGF32EM <.05% of CV A to AB (ANSI
Class III), <.1% of CV B-AB
VGF31LD and VGF32LD <.05% of CV AB to A (ANSI
Class III), <.1% of CV AB-B
PRODUCT DATA
63-2618-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell VGF21

  • Page 1: Specifications

    VGF Flanged Globe Valves PRODUCT DATA SPECIFICATIONS VGF22 Models: See Tables 2 and 3. VGF21 Dimensions: See Fig. 3 and 4. Action: Mixing valves: Stem up to close port A-AB. All others: Stem down to close port A-AB. Controlled Media: Water up to 50% glycol solution.
  • Page 2 3" VGF valves. 60 6 in. ports 43196000-038 High Temperature Kit. Fits 4 to 6" VGF valves. R43176754002 Packing Kit for 2-1/2 in. and 3 in. VGF21 e.g.: 3 in. flanged, equal percent, pressure- and VGF31 valves. VGF2 balanced, ANSI 125 R43176755004 Packing Kit for 2-1/2 in.
  • Page 3 VGF FLANGED GLOBE VALVES LINEAR FLOW EQUAL PERCENTAGE FLOW 100% 100% AB TO B FOR 3 WAY DIVERTING B TO AB FOR 3 WAY MIXING VALVE FLOW FLOW (% OF CV) (% OF CV) A TO AB FOR 2 WAY LS AND LP MODELS AB TO A FOR 3 WAY DIVERTING A TO AB FOR 2 WAY EP AND ES MODELS A TO AB FOR 3 WAY MIXING...
  • Page 4 VGF FLANGED GLOBE VALVES Linear Globe Valve Actuator Models Actuator Part Number Stem Force (lbf) Actuator Valve Characteristics Stroke (inch) 1-1/2 Connection Size Stem Travel Valve Part (inch) (inch) Body Pattern Flow Characteristics Number Close-Off (psi) 2-1/2 Mixing Equal Percentage * VGF31EM25 Mixing Equal Percentage *...
  • Page 5 VGF FLANGED GLOBE VALVES Table 5. Close-off Ratings for VGF valves with Direct Coupled Actuators and Linkages. Rotary Direct Coupled Actuators with Globe Valve Linkage Linkage Part Number Q5020A1003 Q5024B2230 Q5024B2240 Linkage Type Single actuator Dual actuator Dual actuator Stem Adapter / Collar Part Number HU5024-001 HU5024-002...
  • Page 6 VGF FLANGED GLOBE VALVES Rotary Direct Coupled Actuators with Globe Valve Linkage Linkage Part Number Q5020A1003 Q5024B2230 Q5024B2240 Linkage Type Single actuator Dual actuator Dual actuator Stem Adapter / Collar Part Number HU5024-001 HU5024-002 Actuator torque (lb-in) (2x175) (2x300) (2x175) (2x300) Stem Force (lbf) Effective Linkage Stroke...
  • Page 7 VGF FLANGED GLOBE VALVES Modutrol IV Actuators with Q5001 Valve Linkage Linkage Part Number Q5001D1000 Q5001D1018 Q5001D1026 Actuator torque (lb-in) Stem Force (lbf) Valve Characteristics Linkage Stroke (inch) 1-1/2 Stem Connection Size Travel (inch) (inch) Body Pattern Flow characteristics Valve Part Number Close-Off (psi) Class 125 Standard Globe Valves 2-1/2...
  • Page 8 VGF FLANGED GLOBE VALVES Table 7. VGF3 B-Port Threads. Model Thread # of Holes Stroke Y VGF31EM25 0.625-11 VGF31EM30 0.625-11 VGF31EM40 0.625-11 VGF31EM50 0.750-10 VGF31EM60 0.750-10 VGF32EM25 0.750-10 VGF32EM30 0.750-10 VGF32EM40 0.750-10 VGF32EM50 0.750-10 VGF32EM60 0.750-10 VGF31LD25 0.625-11 VGF31LD30 0.625-11 DOTTED LINE REPRESENTS ANSI 125 VGF31LD40 0.625-11...
  • Page 9 VGF FLANGED GLOBE VALVES Table 8. Valve Sizes, Flow Capacities, and Dimensions. Dimensions, in. (mm) Size See Fig. 3 (Two-way Valves) or Fig. 4 (Three-way Valves) Model Number Cv (kvs) Y (stroke) 2-way valves, ANSI Class 125 Stem down to close. Equal percentage or Linear flow characteristic. VGF21_S25 2-1/2 70 (60)
  • Page 10 VGF FLANGED GLOBE VALVES SPRING RANGE PSI (kPa) SIZE 2-1/2 AND 3 IN. D.A. FLANGED BODIES WITH 7 IN. R.A. PNEUMATIC ACTUATOR (NORMALLY CLOSED) (48) (15) (76) (30) (83) (55) (90) (55) (83) (20) (50) (90) (62) (15) (96) (40) (69) (96) (103)
  • Page 11: Installation

    VGF FLANGED GLOBE VALVES SPRING RANGE PSI (kPa) SIZE 2-1/2 IN., 3 IN., 4 IN., 5 IN., 6 IN. WITH 13 IN. D.A. PNEUMATIC ACTUATOR (NORMALLY OPEN PORTS B TO AB) (48) (15) (76) (30) (83) (55) (55) (20) (90) (50) (83) (90)
  • Page 12 They are to be operated with the Disconnect power supply to the actuator to prevent appropriate Honeywell actuators only. Water should be electrical shock and equipment damage, or properly filtered, treated and conditioned according to remove and cap the air line to the actuator.
  • Page 13 VGF FLANGED GLOBE VALVES Location 7. Use mounting bolts long enough so the nuts can use the full length of the nut threads. (See Fig. 11.) Use Select a location where the valve and actuator are bolts 1/8 in. smaller than the diameter of the bolt accessible.
  • Page 14 VGF FLANGED GLOBE VALVES POSITIONER ML6421B ON MP953E ONLY MINUMUM CLEARANCE 7 (178 ) X 7 (178) 2-1/2 (64) 16-7/8 (430) MINIMUM CLEARANCE MP953E 12-3/4 (326) MP953C KNOCKOUTS 7/8 (22) 11-7/8 (301) MP953C, E (204) OPERATION SIZE NOMINAL DIA 8-INCH 8-1/4 (210) 11-1/8 (283) 6-1/2 (165)
  • Page 15 VGF FLANGED GLOBE VALVES 4-5/8 (117) 5-5/15 6-5/16 14-5/16 (364) (135) (161) MINIMUM 2-11/16 (67) CLEARANCE 11-1/4 (284) 9-1/2 (241) 1/2 (13) FPT 7-5/8 (192) 6-9/16 YOKE (166) DIAMETER 1-3/8 (35) M7892A Fig. 16. ML6425A,B; ML7425A,B Actuator (use with 2-1/2 and 3 in. valves) dimensions in in. (mm). 1-7/8 (48) Q5020A,B,D: 4-7/16 (112)
  • Page 16: Operation

    (See dimension Y, in Table 8.) Dimension Y is measured from the closure of the A port. Fig. 20. Two-way standard valve operation. Honeywell actuators are constructed to this Y dimension, and limit stem travel accordingly. Three-Way Valves Flow does not increase with stem travel greater than 3/4 Figs.
  • Page 17 Note that the full stroke of the valve stem can be greater than the control stroke dimension, Y, in Table 8, which is measured from the closure of the A port. Honeywell actuators are constructed for this Y dimension, and limit stem travel appropriately.
  • Page 18 VGF FLANGED GLOBE VALVES VGF31EM FULL HEAT PUMP HEATING COIL VGF3 5 GPM BOILER 5 GPM M36099 PROPORTIONED Fig. 24. Supply mixing for reset control. HEAT VGF3 MIXED DISCHARGE WATER TO 2.5 GPM HEAT LOAD 2.5 GPM CHECK BYPASS 5 GPM VALVES SUPPLY RETURN...
  • Page 19: Checkout And Troubleshooting

    • Limit differential pressure across valve seats to 20 psi. Noisy Valve • This recommendation is independent of published close-off ratings. • Take care not to exceed valve temperature ratings. This can result in damage not covered by the Honeywell limited warranty. Actuator Failure in Steam Applications •...
  • Page 20 VGF FLANGED GLOBE VALVES By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...