Dynamic pressureregulating flanged control valves

Advertisement

Quick Links

VRW2 Dynamic Pressure-
Regulating Flanged Control Valves
APPLICATION
The VRW2 two-way dynamic pressure-regulating control
valves maintain constant flow of hot and chilled water in
closed-loop heating, ventilating, and air conditioning (HVAC)
systems regardless of head pressure fluctuations above
minimum specified pressure drop. These valves come
complete with proportional, stay-in-place or electronic fail-safe
actuators.
The built-in differential pressure regulator makes fluid flow
through the valve independent of changes in supply pressure,
eliminating "hunting" by the control system, even at low coil
flow. The pressure regulator virtually eliminates cavitation in
the valve, and decouples the control valve from the effects of
piping components such as reducers and elbows.
Pressure independent control valves are sized to match
design coil flow regardless of coil size. VRW2 valves eliminate
the need to balance the system for proper flow, and allow
chillers to be operated at design temperature differential for
maximum efficiency at every load condition. When used in a
system with variable speed pump drives, 3-way valves and
coil bypass lines are not required.
Systems that utilize the capabilities of properly installed and
adjusted pressure-independent control valves may qualify for
LEED points.
FEATURES
• Multi-sized bodies from 2½ to 6 inch pipes with wafer-
flanged connections.
• Combination ANSI/ASME Class 150/300 pressure
rating.
• Controls hot or chilled water with up to 50% glycol.
• Regulated flow rates available from 39 to 469 gpm.
• Stainless steel pressure regulator maintains constant
pressure drop across valve seat.
• Positive pressure, rolling diaphragm regulator design
for long service life provides flow control accuracy of
±5%.
• Equal percentage flow characteristic using multi-turn,
non-rising, characterized plug.
• High close-off rating.
• 50 discrete, selectable flow rates available per valve
size.
• Stainless steel trim.
• Six-turn actuator with floating or modulating inputs
available with stay-in-place or electronic fail-safe
action.
• Fail-safe actuators field-configurable for normally
open or normally closed power failure return position.
• Two Test Ports for venting or pressure gauge
attachment.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Operation and Checkout ..................................................
TYPICAL SPECIFICATIONS ............................................ 10
PRODUCT DATA
Contents
1
1
2
2
4
9
62-3116-01

Advertisement

loading

Summary of Contents for Honeywell VRW2

  • Page 1 Contents Pressure independent control valves are sized to match design coil flow regardless of coil size. VRW2 valves eliminate Application ................ the need to balance the system for proper flow, and allow Features ................
  • Page 2 If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES M31295 Fig. 1. Dimensions in in. (mm). Table 2. Dimensions. Model Size Weight S.I. in. (mm) in. (mm) in. (mm) lbs. (kg) VRW2J… 2-1/2 & 3 DN65, DN80 8 3/4 (224) 9 3/4 (246) 3 3/4 (95) 27.8 (10.0)
  • Page 4 -4°F (-20°C) to 228°F (120°C) at a (expansion/contraction of the system and its medium as maximum pressure of 580 psig (40 bar). VRW2 valves are to well as operating pressures) are within tolerances. be operated with supplied multi-turn actuators only.
  • Page 5 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES INCORRECT CORRECT ORIENTATION OF ACTUATOR ABOVE THE VALVE SPINDLE M31296 Fig. 2. Vertical pipe installation. M29519A Fig. 3. Acceptable valve angle from vertical. ACTUATOR WIRING AND PROGRAMMING Shielded cable is recommended when using 0-10 Vdc 1.
  • Page 6 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES Table 4. Maximum Flow Rate Settings. VRW2JV... VRW2JW... VRW2KV... VRW2KW... VRW2LV... VRW2LW... 2-1/2 & 3" 2-1/2 & 3" 3 & 4" 3 & 4" 5 & 6" 5 & 6" (DN65/80) (DN65/80) (DN80/100)
  • Page 7 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES Table 4. Maximum Flow Rate Settings. (Continued) VRW2JV... VRW2JW... VRW2KV... VRW2KW... VRW2LV... VRW2LW... 2-1/2 & 3" 2-1/2 & 3" 3 & 4" 3 & 4" 5 & 6" 5 & 6" (DN65/80) (DN65/80)
  • Page 8 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES Programming Normally Open or Normally Closed Setting The Actuator is delivered from the factory set to the “normally closed” function for an analog control signal so that a minimum #1 OFF signal of 2V or 4mA will close the valve and a maximum signal of...
  • Page 9 3. Rotate valve stem to manually operate valve. Clockwise to close, Counter-Clockwise to open. See Fig. 11. At full flow in a 2-position control application, a VRW2 behaves as a flow limiter. OPEN The pressure regulator takes a minimum pressure to operate, and has a maximum differential regulation capability.
  • Page 10 8. Actuators shall provide screw terminal wiring connec- number, and tag location. tions with adapters for flexible conduit where mechanical 7. Valves and actuators shall be as supplied by Honeywell. protection is required by local codes. 9. Valve actuator shall be capable of operating on 24 Vac...
  • Page 11 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES 62-3116—01...
  • Page 12 VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2010 Honeywell International Inc.