Configuration Process; Overview Of Configuration Process - ABB COM600 Station Automation Series User Manual

Com600 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

1MRS756125
4.3.
4.3.1.
COM600 Station Automation Series
User's Guide
Process data accessible on the devices is modeled according to the IEC 61850 standard.
In the communication structure this is seen as logical devices (LD), logical nodes (LN)
and data objects (DO). It is possible to insert an empty device into the structure and then
manually add and configure LD, LN and DO objects. It is also possible to use pre-con-
figured object types of the devices, which have the objects defined and configured to
add efficiency. The device configuration can also be imported from an IED SCL
description. Data objects include configuration properties, that contain cross-referencing
information between protocol and the OPC/IEC 61850.
Process data is connected to a Gateway client using a Cross-Reference function available
in the client IED object. Data objects that are transferred to the client are dragged from
the servers on the structure to the function tool. Cross-referencing information is filled
in the function window. The Cross-Reference function supports import and export with
Microsoft Excel.
When the structure is complete and all the objects have been set up properly the config-
uration is downloaded to the Gateway using the Gateway Management function available
on the Gateway object.

Configuration process

Overview of configuration process

Before you can start using COM600, you need to build and configure the communication
and substation structure of your project in Communication Engineering Tool CET.
Start Communication Engineering Tool (CET) and open and name a project.
1. Select File > Open/Manage Project....
2. In the Open/Manage Project dialog, select the required location for the project:
Projects on my computer
Projects on network
3. Select New Project on the left.
Enter a Project Name. The Description is optional.
4. Click Create.
5. Click Open Project.
Note that a project can have only one Gateway configuration.
Figure 4.3.1-1 shows an example view of CET including an object tree in the Commu-
nication structure on the left and property window displaying the object properties on
the right.
COM600 3.2
33