Opc Clients - ABB COM600 Station Automation Series User Manual

Com600 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

COM600 3.2
4.3.2.3.
36
COM600 Station Automation Series
User's Guide
To create the substation structure manually:
1. Create Gateway, Substation and Voltage level objects to the substation structure.
2. Add bays and busbars, and design their layout using the SLD Editor. Connect your
substation structure objects to communication structure (logical nodes) using the
data connection function.
If the configurations of the bays are similar, you can copy the
bay object and the data it contains. This way you do not have
to add each bay separately to the substation structure.
3. Design your voltage level layout by connecting busbars and bays and relocating
them with the SLD Editor. Open the SLD Editor by right-clicking the voltage level
object.
4. Design your substation layout by connecting possible transformer windings between
voltage levels. Relocate voltage levels with the SLD Editor. Open the SLD Editor
by right-clicking the substation.
5. Fine tune SLD settings, for example fonts and colors.
For more detailed information, refer to COM605 COM615 HMI Configuration manual.

OPC clients

The object tree is built in the communication structure. Note that before an OPC client
can be taken into use, an OPC server has to be configured for the process communication.