Hardware; Mechanical Properties - ABB COM600 Station Automation Series User Manual

Com600 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

COM600 3.2
2.4.
2.4.1.
22
COM600 Station Automation Series
User's Guide
Queue priorities
If a high priority queue contains an update, it is always sent first. After that, the interrog-
ated queue is checked. If none of these queues has updates, the state indications and
measurements are checked in round-robin fashion.
Queue capacities
The capacity (maximum size) of each queue is independently configured. If one queue
fills up, capacity from another, possibly non-full queue is not used.

Hardware

Mechanical properties

Mechanical information:
Dimensions (without fastening brackets): 214 mm (W) x 122.5 mm (H) x 313 mm
(L)
Net weight 6.8 kg
Degree of protection IP 4x
EMC CE/FCC class B
Antivibration and antishock tests
Hardware Design:
uggedized mechanics:
No moving parts - no fans, no hard disks
System:
Intel® Pentium® M 1.6 GHz
1 GB SDRAM System Memory
2 GB Industrial SSD Compact Flash memory
Watchdog timer
Interfaces:
3 x RS 232 serial ports DB9 male connector
1 x RS 232/485 serial port DB9 male connector
2 x 10/100Base-TX RJ-45 connector
4 x USB 2.0 port
Optional PCI extensions:
1 x LON interface
8 x RS485 serial interfaces
2 x 10/100Base-TX RJ-45 connector
1 x VGA display connector
1 x Audio connector (adapter cable for 3.5 mm stereo plug included)
Power supply units:
high voltage: 76 to 240 V dc