Siemens SIMATIC NET CP 243-2 Manual page 99

As-interface master
Table of Contents

Advertisement

Meaning of the Flags
OFFLINE_READY
APF
NORMAL_MODE
CONFIG_MODE
AUTO_ADDR_AVAIL
AUTO_ADDR_ASSIGN
LDS_0
CONFIG_OK
OFFLINE
EEPROM_OK
AUTO_ADDR_ENABLE
INTERNAL
PERIPHERY_FAULT
MPO startup
meaning of the bits in the lists:
Bit = 0:
Bit = 1:
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
The flag is set when the offline phase is active.
This flag is set when the voltage on the AS-i cable is too low.
This flag is set when the CP 243-2 is in the normal mode.
The flag is set in the configuration mode and reset in the protected mode.
This flag is set when the automatic address programming can be executed
(in other words exactly one slave is currently out of operation).
This flag is set when the automatic address programming is possible (in
other words AUTO_ADDR_ENABLE = 1 and there is no "incorrect" slave
connected to the AS-i cable).
This flag is set when a slave exists with address 0.
This flag is set when the desired (configured) and actual configuration
match.
This flag is set when the CP is to change to the OFFLINE mode or is
already in this mode.
This flag is set when the test of the internal EEPROM did not detect any
errors.
This flag indicates whether the automatic address programming is enabled
(BIT = 1) or disabled (BIT = 0) by the user.
This flag is always set.
This flag is set when at least one AS-i slave is signaling a peripheral fault.
The "master_power_on_startup" flag is set after the power supply of the
AS-i master has been turned on. If the master is later
changed to OFFLINE, the bit is reset.
AS-i slave is not activated (detected, configured)
AS-i slave is activated (detected, configured)
Command Interface
5-31