Siemens SIMATIC NET CP 243-2 Manual page 125

As-interface master
Table of Contents

Advertisement

5.2.31
Read_AS-i_Slave_Diagnostic_String
Purpose
With this call, an diagnostic string complying with the AS-i slave profile 7.4 can be
read from the AS-i slave with the AS-i slave address specified in the send buffer.
The AS-i master supplies up to 223 bytes of reply data. The number of diagnostic
bytes actually sent by the AS-i slave is signaled by the AS-i master in byte 2 of the
receive buffer (number of diagnostic bytes).
If the AS-i slave sends a string longer than 220 bytes, the AS-i master aborts the
string transfer and terminates the job with an error. The received data are then not
made available to the user program.
As long as the string transfer is active, there is no user/analog data exchange with
the addressed AS-i slave.
Structure of the Job Data in the Send Buffer
Bank
Byte
2
0
2
1
Structure of the Job Data in the Receive Buffer
Bank
Byte
2
0
2
1
2
2
2
3
2
4
...
...
...
...
...
...
Maximum value for n=220
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Meaning
Command number 43
H
Slave address
Meaning
Echo of the command number 43
Command status
Number of diagnostic bytes
String byte (1)
String byte (2)
.....
String byte (n–1)
String byte (n)
Command Interface
H