Command Status
Whether or not the job was executed correctly or errors occurred is signaled in the
command status of the response buffer in byte 1.
Table 5-6
Value
00
H
81
H
82
H
83
H
84
H
85
H
86
H
A1
H
A2
H
A3
H
A4
H
A5
H
A6
H
A7
H
A8
H
B1
H
B2
H
F8
H
F9
H
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Job completed without error
The AS-i slave address is incorrect
The AS-i slave is not activated (not in LAS).
Error on AS-Interface.
Command not permitted in the current status of the AS-i master.
An AS-i slave with address 0 exists.
The AS-i slave has illegal configuration data (I/O or ID codes).
The addressed AS-i slave was not found on the AS-Interface.
An AS-i slave with address 0 exists.
An AS-i slave with the new address already exists on the AS-Interface.
The AS-i slave address cannot be deleted.
The AS-i slave address cannot be set.
The AS-i slave address cannot be stored permanently.
Error reading the extended ID1 code.
The target address is not plausible (for example a B slave address was
used for a standard slave).
A length error has occurred transferring a string according to profile 7.4.
A protocol error has occurred transferring a string according to profile
7.4.
The job number or the job parameter is unknown.
The AS-i master has detected an EEPROM error.
Command Interface
Meaning