Siemens SIMATIC NET CP 243-2 Manual page 25

As-interface master
Table of Contents

Advertisement

Note
Changing from the configuration mode to the protected mode is only possible
when there is no slave with address "0" connected to the AS-Interface. If a slave
"0" is connected, the "SF" LED lights up when the SET button is pressed.
Preparing to Configure
Make sure that the following situation applies:
The S7-22x CPU must be set to STOP (PLC_RUN=0).
The CP 243-2 and all AS-i slaves must be connected to the AS-Interface and
supplied with power by the AS-i power supply.
Configuring
1. Press the DISPLAY button to set the CP 243-2 display to the "status display"
mode (initial status).
2. Check whether the CP 243-2 is in the "configuration mode". ("CM" LED lit ). If
not, change the CP 243-2 to the configuration mode using the SET button.
3. By changing to the slave display with the DISPLAY button, you can check
whether all the slaves connected to the AS-Interface exist.
4. Press the SET button. The CP 243-2 is configured.
At the same time, the CP 243-2 is changed to the protected mode; the "CM"
LED goes off.
The "CER" LED also goes off since following configuration, the "expected
configuration" stored on the CP 243-2 matches the "actual configuration" on the
AS-Interface.
Note
Configuring the CP 243-2 during an AS-Interface Power Fail (for example when
the AS-i power supply unit is turned off or when the CP 243-2 is not connected to
the AS-Interface) resets the configuration of the CP 243-2. This has the following
results:
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Technical Description and Installation Instructions
No AS-i slaves are configured;
All AS-i slave parameters are set;
Automatic address programming is activated
(bit AUTO_ADDRESS_ENABLE = 1).
1-17