Siemens SIMATIC NET CP 243-2 Manual page 92

As-interface master
Table of Contents

Advertisement

Command Interface
5.2.12
Select_Autoprogramming
Purpose
This call can enable or disable the "automatic address programming" function (see
also Section 6.1).
The AUTO_ADDR_ENABLE bit is stored permanently; in other words it is retained
after a warm/hot restart on the AS-i master.
Structure of the Job Data in the Send Buffer
Bank
Byte
2
0
2
1
Structure of the Job Data in the Receive Buffer
Bank
Byte
2
0
2
1
5-24
Bit 7
Command number: 0B
reserved
Echo of the command number: 0B
Command status
Meaning
Bit 1
H
Value for AUTO_ADDR_ENABLE
1=Automatic address programming
enabled
0=Automatic address programming
disabled
Meaning
H
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Bit 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents