Siemens SIMATIC TIWAY 1 User Manual page 70

Unilink host adapter
Hide thumbs Also See for SIMATIC TIWAY 1:
Table of Contents

Advertisement

CONFIGURING THE HOST COMPUTER PORT
3.3.1.1 Setting the Host Port Parameters
The host port communication parameters are configured with two 10-position
dipswitches located at the front of the adapter as shown in Figure 3–3. To select
NITP as the operating protocol, set position 1 of Dipswitch 1 up as shown in
Figure 3–10.
UNILINK HOST ADAPTER
USER MANUAL
DIPSWITCH 1
1
2
3
4
5
6
7
8
U
P
UP=NTP
DIPSWITCH 2
1
2
3
4
5
6
7
8
U
P
MSB
LSB
UP
= SYNCHRONOUS
DOWN = ASYNCHRONOUS
UP
= FULL DUPLEX
DOWN = HALF DUPLEX
UP
= EVEN PARITY
DOWN = ODD PARITY
UP
= PARITY ENABLED
DOWN = PARITY DISABLED
Figure 3–10 NITP Dipswitch Settings
The host port parameters specify the physical layer
protocol parameters and do not imply that the data
link protocols can be either asynchronous or
synchronous. Both the BDLC and NITP protocols are
asynchronous data link layer protocols.
KEY
9 10
UP DOWN
HOST COMMAND
TIMEOUT
9
10
UP
= TEST MODE
DOWN = RUN MODE
UP
= HIU/EHA &
IO LOOP TEST
DOWN = MHIU/EHA
HOST PORT BAUD RATE
HOST PORT
HOST PORT
HOST PORT
HOST PORT
NOTE
3–12

Advertisement

Table of Contents
loading

Table of Contents